Installation Guide
11
Sizing Methods and Examples
routed to each appliance location. Manifold stations are located as close as possible to the 
appliance(s) with the greatest load. Parallel layouts are most commonly used in ¼ to ½ PSI 
systems.
Dual Pressure Systems
Elevated pressure systems generally have a main line from the gas supply to one or more 
gas pressure regulators and then a manifold with "home runs" to appliances. These runs may 
branch o through use of a tee, if gas loads permit.
Elevated Pressure System
It is also possible to have 
a complete elevated 
pressure system where 
the pressure regulators 
are positioned at each 
appliance. This method 
is typically employed in 
systems with high loads 
or long runs.
Multiple Manifold System
Another variant used 
with elevated pressure 
is to have multiple man-
ifolds, each with a regulator before the manifold. This approach allows for large BTU load 
demands while using smaller diameter tubing.
Hybrid Systems (Rigid pipe and CSST)
The use of both CSST and rigid black pipe can be advantageous to minimize the pressure 
drops typically encountered on systems with high loads or long runs. For example, a paral-
lel system could require a larger diameter main branch to provide the total appliance load. 
HOME-FLEX® is certied for use with black steel pipe and copper tubing gas piping systems.
3.2  Sizing Methods and Examples
This section will outline sizing procedures under several dierent circumstances to demon-
strate how to select the proper size and conguration of HOME-FLEX® exible gas tubing. 
These examples are presented to demonstrate the process of using sizing tables to determine 
necessary pipe size and conguration. Every installation is dierent and this requires that the 
installer go through the processes outlined below for the proper sizing and conguration of 
the gas piping system given the circumstances and requirements at the installation location.
Sizing Tables
All piping systems introduce pressure loss, the amount of which depends on the piping size 
and the gas ow (in cubic feet per hour). When "sizing" a system, the installer determines the 
smallest size piping that will deliver the ow required given the allowable amount of pres-
sure drop. Sizing tables provide the maximum load for a run given the gas pressure, allowable 
pressure drop, size of pipe and the length of the run. Dierent sizing tables are used for each 
combination of system pressure and pressure drop. 
Allowable pressure drop is the maximum pressure loss that can occur and maintain supply 
pressure for proper equipment or appliance operation. Natural gas appliances are generally 
designed to function with a minimum pressure of 4 inches w.c. LP appliances are generally 
designed for a minimum pressure of 10 inches w.c. The sizing tables in this guide should be 
used to provide no less than 5 inches w.c. to natural gas appliances and 10.5 inches w.c. to LP 
appliances. Allowable pressure drop can be calculated by subtracting the desired appliance 
Gas 
Meter
25,000 BTUH
Range Oven
40,000 BTUH
Elevated 
Pressure
60,000 BTUH30,000 BTUH
Furnace
Water 
Heater
Dryer
Figure 3.3  A dual pressure system layout










