TABLE 9
Location Of Circular Holes In P3 Joist Webs
Simple or Multiple Span for Dead Loads up to 10 psf and Live Loads up to 40 psf
1,2,3,4
Cutting the Holes
• Never drill, cut, or notch the flange� Never over-cut the web�
• Holes in webs should be cut with a sharp saw�
• For rectangular holes avoid over cutting the corners as this can cause unnecessary stress concentrations� Slightly rounding the corners
is recommended� Starting the rectangular hole by drilling a 1” diameter hole in each of the4corners and then making the cuts between
the holes is another good method to minimize damage to I-Joist�
Joist
Depth
Joist
Minimum distance from inside face of any support to center of hole (ft-in�)
Round Hole Diameter (in�)
SAF
(5)
2 3 4 5 6 6-1/4 7 8 8-5/8 9 10 10-3/4 11 12 12-3/4
9-1/2”
PJI 40 14’-6” 0’-7” 1’-8” 3’-0” 4’-4” 5’-9” 6’-3” 2 N 1 2 X
PJI 60 15’-3” 1’-8” 3’-0” 4’-4” 5’-8” 7’-3” 7’-8” 2 N 1 2 X
11-7/8”
PJI 40 16’-7” 0’-7” 0’-8” 1’-2” 2’-5” 3’-9” 4’-1” 5’-1” 6’-8” 7’-11” 1 2
PJI 60 18’-2” 0’-8” 1’-10” 3’-2” 4’-5” 5’-10” 6’-2” 7’-4” 8’-11” 10’-0” 1 2
PJI 80 19’-10” 1’-11” 3’-2” 4’-6” 5’-10” 7’-3” 7’-8” 8’-10” 10’-6” 11’-7” 1 2
PJI 90 20’-5” 2’-1” 3’-4” 4’-8” 6’-0” 7’-6” 7’-10” 9’-0” 10’-8” 11’-11” 1 2
14”
PJI 40 18’-3” 0’-7” 0’-8” 0’-8” 0’-9” 1’-10” 2’-2” 3’-2” 4’-7” 5’-5” 6’-0” 7’-7” 9’-4”
PJI 60 19’-9” 0’-7” 0’-8” 0’-8” 1’-7” 3’-2” 3’-6” 4’-9” 6’-6” 7’-8” 8’-4” 10’-4” 11’-11”
PJI 80 22’-7” 0’-7” 1’-9” 3’-0” 4’-4” 5’-8” 6’-1” 7’-1” 8’-7” 9’-7” 10’-3” 12’-2” 13’-10”
PJI 90 23’-2” 0’-7” 1’-9” 3’-0” 4’-4” 5’-8” 6’-1” 7’-1” 8’-8” 9’-10” 10’-7” 12’-8” 14’-4”
16”
PJI 40 19’-8” 0’-7” 0’-8” 0’-8” 0’-9” 0’-9” 0’-10” 1’-5” 2’-9” 3’-7” 4’-1” 5’-6” 6’-7” 7’-0” 8’-9” 10’-9”
PJI 60 19’-9” 0’-7” 0’-8” 0’-8” 0’-9” 0’-9” 0’-10” 1’-10” 3’-6” 4’-6” 5’-2” 7’-3” 8’-11” 9’-6” 11’-10” 13’-9”
PJI 80 23’-11” 0’-7” 0’-8” 0’-8” 1’-7” 3’-2” 3’-7” 4’-10” 6’-6” 7’-7” 8’-3” 10’-2” 11’-8” 12’-2” 14’-3” 16’-0”
PJI 90 25’-5” 0’-7” 0’-8” 1’-8” 2’-11” 4’-3” 4’-7” 5’-7” 7’-0” 8’-1” 8’-9” 10’-8” 12’-2” 12’-8” 14’-10” 16’-7”
18”
PJI 80 27’-3” 0’-7” 0’-8” 0’-8” 0’-11” 2’-3” 2’-8” 3’-9” 5’-2” 6’-1” 6’-8” 8’-3” 9’-6” 9’-11” 11’-8” 13’-0”
PJI 90 27’-11” 0’-7” 0’-8” 0’-8” 1’-6” 2’-11” 3’-4” 4’-5” 5’-10” 6’-10” 7’-5” 9’-0” 10’-3” 10’-8” 12’-5” 13’-9”
20”
PJI 80 29’-6” 0’-7” 0’-8” 0’-8” 0’-9” 1’-9” 2’-1” 3’-1” 4’-5” 5’-3” 5’-10” 7’-3” 8’-4” 8’-8” 10’-3” 11’-5”
PJI 90 30’-3” 0’-7” 0’-8” 0’-8” 0’-10” 2’-2” 2’-6” 3’-6” 4’-10” 5’-8” 6’-2” 7’-8” 8’-9” 9’-1” 10’-8” 11’-11”
22”
PJI 80 31’-5” 0’-7” 0’-8” 0’-8” 0’-9” 0’-9” 1’-1” 2’-0” 3’-3” 4’-0” 4’-6” 5’-9” 6’-9” 7’-1” 8’-6” 9’-9”
PJI 90 31’-5” 0’-7” 0’-8” 0’-8” 0’-9” 0’-10” 1’-1” 2’-0” 3’-3” 4’-2” 4’-9” 6’-4” 7’-7” 8’-0” 9’-8” 11’-0
24”
PJI 80 31’-5” 0’-7” 0’-8” 0’-8” 0’-9” 0’-9” 0’-10” 0’-10” 1’-11” 2’-7” 3’-1” 4’-4” 5’-5” 5’-10” 7’-4” 8’-6”
PJI 90 31’-5” 0’-7” 0’-8” 0’-8” 0’-9” 0’-9” 0’-10” 0’-10” 2’-4” 3’-2” 3’-9” 5’-3” 6’-4” 6’-9” 8’-4” 9’-6”
NOTES
1� Above tables may be used for P3 Joist spacing of 24” on center or less�
2� Hole location distance is measured from inside face of supports to center of hole�
3� Distances in this chart are based on uniformly loaded joists�
4� Hole sizes and/or locations that fall outside of the scope of this table may be
acceptable based on analysis of actual hole size, span, spacing, and loading conditions�
5� SAF stands for Span Adjustment Factor� SAF is used as defined below�
OPTIONAL
Table 9 is based on the P3 Joists being used at their maximum span� If the P3Joists
are placed at less than their full allowable span, the maximum distance from
thecenterline of the hole to the face of any support (D) as given above may be
reduced as follows�
D
reduced
= L
actual
x D
SAF
Where: D
reduced
= Distance from the inside face of any support to center of hole is
reduced for less-than-maximum span applications (ft)� The reduced
distance shall not be less than 6” from the face of support to edge
of the hole�
L
actual
= The actual measured span distance between the inside faces of
supports (ft)
SAF = Span Adjustment Factor is given in the table above�
D = The minimum distance from the inside face of any support to
center of hole from Table 9 above
If L
actual
is greater than 1, use 1 in the above calculation for L
actual
�
SAF SAF
P3 Joist Typical Holes
FIGURE 6
See rule 11�Minimum distance from face of support
to the center of hole (See Table 9)
3/4x
diameter
2x diameter
of larger hole