Installation Guide

Framer Series
Lumber Specier’s Guide TJ-4020
|
May 2014
3
FRAMER SERIES
LUMBER SPAN AND LOAD TABLES
Framer Series
lumber is intended
for dry-use applications
Maximum Floor Spans
(1)
Nominal
Size
Width Depth
40 psf Live Load,
10 psf Dead Load, L/360
(2)
40 psf Live Load,
10 psf Dead Load, L/480
30 psf Live Load
(3)
,
10 psf Dead Load, L/360
(2)
30 psf Live Load
(3)
,
10 psf Dead Load, L/480
12" o.c. 16" o.c. 19.2" o.c. 24" o.c. 12" o.c. 16" o.c. 19.2" o.c. 24" o.c. 12" o.c. 16" o.c. 19.2" o.c. 24" o.c. 12" o.c. 16" o.c. 19.2" o.c. 24" o.c.
2x8 " 7¼" 14'-2" 12'-10" 12'-1" 11'-3" 12'-10" 11'-8" 11'-0" 10'-2" 15'-7" 14'-2" 13'-4" 12'-4" 14'-2" 12'-10" 12'-1" 11'-3"
2x10 " 9¼" 18'-0" 16'-5" 15'-5" 14'-4" 16'-5" 14'-11" 14'-0" 13'-0" 19'-10" 18'-0" 17'-0" 15'-9" 18'-0" 16'-5" 15'-5" 14'-4"
2x12 " 11¼" 21'-11" 19'-11" 18'-9" 17'-5" 19'-11" 18'-1" 17'-0" 15'-10" 24'-2" 21'-11" 20'-8" 19'-2" 21'-11" 19'-11" 18'-9" 17'-5"
(1) Maximum available length is 20'.
(2) Minimum criteria per code. For stricter deflection criteria, use shorter spans or the L/480 spans.
(3) 30 psf live load is permitted in residential sleeping areas by some codes.
Joist, Beam, or Header Allowable Loads (PLF)
Clear
Span
Condition
1½" Width 3" Width (2-ply) 4½" Width (3-ply) 6" Width (4-ply)
2x8 2x10 2x12 2x8 2x10 2x12 2x8 2x10 2x12 2x8 2x10 2x12
4'
Total Load 799 1,180 1,556 1,599 2,361 3,113 2,548 3,542 4,670 3,397 4,723 6,227
Live Load 799 1,180 1,556 1,599 2,361 3,113 2,548 3,542 4,670 3,397 4,723 6,227
Min. End Bearing (in.) 3.0 3.0 4.5 3.0 3.0 4.5 3.0 3.0 4.5 3.0 3.0 4.5
6'
Total Load 372 591 849 744 1,183 1,698 1,277 2,023 2,660 1,702 2,698 3,547
Live Load 372 591 849 744 1,183 1,698 1,277 2,023 2,660 1,702 2,698 3,547
Min. End Bearing (in.) 1.5 3.0 4.5 1.5 3.0 4.5 3.0 3.0 4.5 3.0 3.0 4.5
8'
Total Load 211 340 496 423 681 992 729 1,170 1,700 972 1,561 2,267
Live Load 211 340 496 423 681 992 637 1,170 1,700 849 1,561 2,267
Min. End Bearing (in.) 1.5 3.0 3.0 1.5 3.0 3.0 1.5 3.0 3.0 1.5 3.0 3.0
10'
Total Load 135 219 322 271 439 644 468 757 1,108 624 1,009 1,477
Live Load 110 219 322 221 439 644 330 676 1,108 440 902 1,477
Min. End Bearing (in.) 1.5 1.5 3.0 1.5 1.5 3.0 1.5 3.0 3.0 1.5 3.0 3.0
12'
Total Load 93 152 224 187 305 449 282 526 775 376 702 1,033
Live Load 64 132 224 128 265 449 193 396 703 257 528 938
Min. End Bearing (in.) 1.5 1.5 3.0 1.5 1.5 3.0 1.5 1.5 3.0 1.5 1.5 3.0
14'
Total Load 58 111 165 117 223 330 175 367 570 234 489 760
Live Load 40 84 149 81 168 299 122 251 447 163 335 597
Min. End Bearing (in.) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 3.0 1.5 1.5 3.0
16'
Total Load 38 81 126 77 162 252 115 244 436 154 325 581
Live Load 27 56 101 54 113 202 82 169 302 109 226 402
Min. End Bearing (in.) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
18'
Total Load 26 56 99 52 112 198 78 169 308 105 225 411
Live Load 19 39 71 38 79 142 57 119 213 77 159 284
Min. End Bearing (in.) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
20'
Total Load 18 40 74 37 80 148 55 121 222 74 161 296
Live Load 14 29 52 28 58 104 42 87 156 56 116 208
Min. End Bearing (in.) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Nominal
Size
Width Depth
20 psf Live Load,
10 psf Dead Load, L/240
(2)
30 psf Live Load,
10 psf Dead Load, L/240
(2)
12" o.c. 16" o.c. 19.2" o.c. 24" o.c. 12" o.c. 16" o.c. 19.2" o.c. 24" o.c.
2x8 " 7¼" 20'-5" 18'-6" 17'-5" 16'-2" 17'-10" 16'-2" 15'-3" 14'-2"
2x10 " 9¼" 26'-0" 23'-8" 22'-3" 20'-8" 22'-9" 20'-8" 19'-5" 18'-0"
2x12 " 11¼" 31'-8" 28'-9" 27'-1" 25'-1" 27'-8" 25'-1" 23'-7" 21'-11"
Maximum Rafter Spans
(1)
(1) Maximum available length is 20'.
(2) Based on 115% duration of load (snow areas).
Nominal
Size
Width Depth
20 psf Live Load,
10 psf Dead Load, L/240
(2)
10 psf Live Load,
5 psf Dead Load, L/240
(2)
12" o.c. 16" o.c. 19.2" o.c. 24" o.c. 12" o.c. 16" o.c. 19.2" o.c. 24" o.c.
2x8 " 7¼" 20'-5" 18'-6" 17'-5" 16'-2" 25'-8" 23'-4" 21'-11" 20'-5"
2x10 " 9¼" 26'-0" 23'-8" 22'-3" 20'-8" 32'-9" 29'-9" 28'-0" 26'-0"
2x12 " 11¼" 31'-8" 28'-9" 27'-1" 25'-1" 39'-10" 36'-2" 34'-1" 31'-8"
Maximum Ceiling Spans
(1)
(1) Maximum available length is 20'.
(2) Based on 100% duration of load.
General Notes for Joist, Beam,
or Header Load Table
Table is based on:
M-12, Southern pine design values (see page 2)
Deflection criteria of L/240 total load, L/360
live load, and 100% duration of load
Allowable loads shown are the maximum uniform
loads (plf) that can be applied to the beam in
addition to its own weight, provided that the
minimum end-bearing requirements are met.
Beams and girders must bear on load-bearing
walls, piles, or concrete or masonry foundations.
For framing instructions, including
recommended fastening schedules, please refer
to the AWC Wood Frame Construction Manual or
your applicable building code.
General Notes for Floor, Rafter,
and Ceiling Span Tables
Table is based on M-12, Southern pine design
values (see page 2).
Maximum available length is 20'.
Joists must bear directly on beams, girders,
ledgers, or load bearing walls; or be supported
by hangers or framing anchors.
Spans shown are horizontal clear distances
between supports, and assume uniformly loaded
joists only.
Minimum bearing: 1½" on wood or steel, 3"
on masonry. Bearing across full joist width is
required.
Provide lateral restraint at the end of each joist
by fastening to a rim, band joist, header, or
other member or by using full-height blocking
between floor joist ends.