Table 4275-1 Reason For Resting
VALUE
REASON FOR RESTING
1
Anti-Click. Not enough power available (Wake Up)
2
Insane Ibatt Measurement (Wake Up)
3
Negative Current (load on PV input ?) (Wake Up)
4
PV Input Voltage lower than Battery V (Vreg state)
5
Too low of power out and Vbatt below set point for > 90 seconds
6
FET temperature too high (always shows up on boot up) (Cover is on maybe ?)
7
Ground Fault Detected
8
Arc Fault Detected
9
Too much negative current while operating
10
Battery is less than 8.0 Volts
11
PV input is available but V is rising too slowly. Low Light or bad connection
12
Voc has gone down from last Voc or low light. Re-check
13
Voc has gone up from last Voc enough to be suspicious. Re-check
14
Same as 11
15
Same as 12
16
Mppt MODE is OFF (Usually because user turned it off)
17
PV input is higher than operation range (too high for 150V Classic)
18
PV input is higher than operation range (too high for 200V Classic)
19
PV input is higher than operation range (too high for 250V or 250KS)
25
Battery Voltage too high of Overshoot (small battery or bad cable ?)