DO YOU KNOW THE BATTERY BANK AMP HR
CAPACITY
YES NO
Helps set Absorption time and EQ defaults
WHAT IS THE VOLTAGE
OF AN INDIVIDUAL
BATTERY
6
This is necessary for the set up software to help
figure out battery capacity
SET CURRENT LIMIT
80
ENTER TO CONTINUE
Sets classic‘s max output current
CONTROLLER MODE
SOLAR WIND HYDRO
SCROLL < > TO SELECT
THEN PUSH ENTER
Selects classic‘s mode. This can be changed in
the mode menu
STC
MODULE POWER
210 ^ WATTS
Photovoltaic module power rating
STC
VOC RATING
44.3^ VOLTS
Photovoltaic module voltage rating
STC
ISC RATING
Photovoltaic module current rating
Setting Nominal Battery voltage
Upon initialization the Classic will display battery
To set up the Classic to a preset battery voltages (e.g. 12v, 24v… 48v) follow the steps below.
Press Main Menu
Scroll to the left until Charge is highlighted and push the Enter button
Highlight Volts and press the Enter button
Press the Right soft key
Scroll up and down to select the desirable battery voltage
Battery Charge Stages and Meanings
Bulk MPPT
This stage of the Classic means; that the Classic will be putting out as much current as it can trying to
charge the batteries to the absorb voltage set point. This is also known as constant current mode.
Absorb
This stage means that the Classic will maintain the absorb set point voltage until the batteries are charged
or it reach Float stage. At this stage the classic is not putting out maximum current, as that would increase
the battery voltage over the Absorb set point. This is also referred to as constant voltage mode.
The absorb time is proportional to the bulk time. (i.e. the time bulk takes to reach the absorb voltage.) The
battery it‘s considered ―full‖ at the end of the absorb charge cycle.