Manual
20 | P a g e
DC GFP (Ground Fault Protection)
The Classic has internal ground fault protection (GFP) built in. Since 2008 the NEC requires a DC-GFP
on all PV systems in the USA. The built in DC-GFP eliminates the need to purchase and install an
external DC-GFP. If the internal grounding jumper is installed in a Classic, the battery negative and DC
source negative must not be connected to the system grounding conductor anywhere in the system.
Grounding of these circuits will defeat the GFP function. In a network with multiple Classics, all
Classics must have the internal grounding jumper installed and GFP enabled. The factory setting will
make a DC negative to System Ground connection in the Classic charge controller. The GFP function
will need to be disabled for Positive ground or an ungrounded DC system.
Figure 2.1
The Ground fault device is simple to understand
and use. The Classic DC-GFP works a bit
different than others. It detects a fault between
battery/PV negative and earth ground just like the
breaker DC-GFP system. The difference with the
Classic is that it simply turns off when a ground
fault is detected. This is different than
disconnecting the PV plus circuit. This trick of
turning off was first pioneered by another charge
control company as an alternative to a $100
external circuit breaker assembly. The Classic‘s
system consists of a PTC that is between the
Negative and Ground internally in the Classic. A PTC is basically a type of resistor with a 1 ohm value
that when loaded to three quarters of an amp will heat up and go to a very high resistance looking like
an open circuit. One of the 3 Classic microprocessors watches the PTC and when it sees a high
resistance it will disable the Classic. The ground fault device will then require a manual reset. The PTC
is self-healing though so there are no fuses to change. This method meets the requirement for DC
ground fault protection in the National Electric Code.
To disable the internal Ground Fault Protection function, the jumper labeled GFP needs to be removed,
and the GFP function must be disabled in the TWEAKS menu. See section below for instructions.
To reset the internal GFP function after detection has occurred, fix the actual ground fault, then turn
OFF the Classic and turn it back ON. Do this by turning the external battery breaker to OFF position
and then to ON position.
Disabling GFP
The GFP feature should only be disabled to operate the Classic in an ungrounded power system or in
systems where GFP is not required.
Press Main Menu
Scroll to the right or left until TWEAKS is highlighted and press ENTER
In TWEAKS press the right soft key to get to the MORE menu
In MORE scroll until GFP is highlighted
Use the up and down arrow keys to toggle between on and off
Press ENTER to save










