Instruction manual
Upstream Instruction Manual
Released on 1-May-14 – R800001Q Page 8 UV Pure Technologies Inc. © 2014
Product Specifications Table
Models NC10-75 NC10-50 NC15-75 NC15-50
NC30-75
1"
NC30-75
1.5"
Max. Flow
Rate
1
11 gpm
41
L/min
2.4 m
3
/hr
11 gpm
41 L/min
2.4 m
3
/hr
16.5
gpm
62
L/min
3.7 m
3
/hr
14.6
gpm
55
L/min
3.3 m
3
/hr
28.5 gpm
108
L/min
6.47 m
3
/hr
28.5 gpm
108
L/min
6.47 m
3
/hr
Nominal
Flow Rate
1
10 gpm
38 L/min
2.3 m
3
/hr
10 gpm
38 L/min
2.3 m
3
/hr
15 gpm
57 L/min
3.4 m
3
/hr
13.2
gpm
50 L/min
3.0 m
3
/hr
26.4 gpm
1
00 L/min
6 m
3
/hr
26.4 gpm
100 L/min
6 m
3
/hr
min. UVT 75% 50% 75% 50% 75% 75%
Operating
Pressure
2
0-
100 psig
0-690 kPa
0-
100 psig
0-690 kPa
0-
100 psig
0-690 kPa
0-
100 psig
0-690 kPa
0-
100 psig
0-690 kPa
0-
100 psig
0-690 kPa
Water
Temp.
range
4
34-
104° F
1-40° C
34-
104° F
1-40° C
34-
104° F
1-40° C
34-
104° F
1-40° C
34-
104° F
1-40° C
34-
104° F
1-40° C
Air Temp.
range
4
34-
104° F
1-40° C
34-
104° F
1-40° C
34-
104° F
1-40° C
34-
104° F
1-40° C
34-
104° F
1-40° C
34-
104° F
1-40° C
Voltage
3
115Vac 115Vac 115Vac 115Vac 115Vac 115Vac
Power Draw 135W 175W 175W 200W 200W 200W
Dry Contact Yes Yes Yes Yes Yes Yes
Remote
Monitor
Optional Optional Optional Optional Optional Optional
Remote
Start/Stop
Yes Yes Yes Yes Yes Yes
Flow
Restrictor
Yes Yes Yes Yes Yes No
Pressure Drop
at 75% rated
capacity
14 psig
(96 kPa)
14
psig
(96 kPa)
14 psig
(96 kPa)
14
psig
(96 kPa)
14
psig
(96 kPa)
4
psig
(28 kPa)
Inlet & Outlet
Port size
1" MNPT
1" MNPT 1" MNPT 1" MNPT 1" MNPT 1.5" MNPT
Nominal
Dimensions
(L x W x D)
32x8x9"
(81x20x
23cm)
36x8x9"
(91x20x
23cm)
36x8x9"
(91x20x
23cm)
40x8x9"
(101x20x
23cm)
40x8x9"
(101x20x
23cm)
40x8x9"
(101x20x
23cm)
1
Flow rates are given in USgpm.
2
The optional shutoff valve requires min. 10psig to operate.
3
100-240Vac versions available with same operating specifications.
4
In extreme conditions with both low air and water temperatures, a Thermal Abatement Kit
R400074 may be necessary
The Upstream™ model NC 30-75 with 1” manifolds achieves a dose of 40 mJ per cm
2
at
a maximum restricted flow rate of 28.5 US GPM.
The Upstream™ model NC 30 with 1 ½” manifolds achieves a dose of 40 mJ per cm
2
at
a maximum unrestricted flow rate of 28.5 US GPM. There is no flow restrictor installed as
standard on this model of Upstream, therefore, a flow rate below 28.5 GPM will result in a
dose greater than 40 mJ per cm
2
, and conversely, a flow rate greater than 28.5 US GPM
will result in a lower dose. This model is designed to allow for low pressure drop
applications and can be programmed to achieve target deactivation levels in a broad range
of applications and pre-treatment water quality, in combination with external flow restriction.