Instruction manual
Remote Station - Guide Point Adjust
94
Hidden
H i d d e n 2 F
This parameter can be configured to hide unused
parameters. If a parameter is Hidden it cannot be selected
or displayed.
The value of this parameter is a bit-field and is displayed in
hexadecimal (hex) format. Each bit corresponds to a
particular parameter – setting a bit to ‘1’ hides the
parameter, and setting it to ‘0’ makes it visible. Refer to the
tables on page 95 for bit definitions and hex conversion
information.
To activate the Hidden feature the keypad must be
Locked. If the keypad is Unlocked, then all parameters will
be visible, regardless of the Hidden settings. Refer to page
96 for more information about this feature.
The default value is 2F.
Example: The default value of 2F (hex) corresponds to a
bit-field pattern of 0000:0000:0000:0010:1111. This pattern
hides the Offset 2, Backlight, Hidden, Read-Only, and
Start-Up parameters.
Range: 0 to FFFFF
Read-Only
R e a d - O n l y 0
This parameter can be configured to prevent accidental o
r
unauthorized changes to parameters. If a parameter is
Read-Only it can be displayed but not changed.
The value of this parameter is a bit-field and is displayed in
hexadecimal (hex) format. Each bit corresponds to a
particular parameter – setting a bit to ‘1’ makes the
parameter read-only, and setting it to ‘0’ makes i
t
changeable. Refer to the tables on page 95 for bi
t
definitions and hex conversion information.
To activate the Read-Only feature the keypad must be
Locked. If the keypad is Unlocked, then all parameters can
be changed, regardless of the Read-Only settings. Refe
r
to page 96 for more information about this feature.
The default value is 0.
Example: The default value of 0 (hex) corresponds to a bit-
field pattern of 0000:0000:0000:0000:0000. This pattern
makes all parameters changeable.
Range: 0 to FFFFF