Instruction manual
MICRO 4000
®
 NET Controller 
54 
Example # 2: Input a voltage from a third-party sensor: 
Calculate the Analog Input Scale Factor using the formula below. 
Analog Input Scale Factor = 100 ×
 F ÷ S 
•  If the sensor is connected to Analog Input 1, then enter the result into parameters 43 
and 44. 
If the sensor is connected to Analog Input 2, then enter the result into parameters 45 
and 46. 
Refer to page 17 for more information about setting these parameters. 
F = Full-scale input range (volts). 
•  If the sensor is connected to Analog Input 1, then the value of F is determined by 
parameter 41, as shown in Table 2. 
If the sensor is connected to Analog Input 2, then the value of F is determined by 
parameter 42, as shown in Table 3. 
S = Sensor output scale factor (volts-per-inch). 
Table 2 
Parameter 
41 
Full-Scale 
Input Range 
0  input 1 is off 
1 5 
2 10 
3 20 
Table 3 
Parameter 
42 
Full-Scale 
Input Range 
0  see note below 
1 5 
2 10 
3 20 
Note: If parameter 2 (end-of-travel mode) is set to 1, then F = 5. If parameter 2 is not set 
to 1, then input 2 is off. 