Instruction manual

MICRO 4000
®
NET Controller
51
Example # 1: Input a sensor signal from another MICRO 4000 NET controller:
In this example controller # 1’s analog input is configured to receive a sensor signal from
controller # 2.
Find the model number of controller # 2’s sensor in Table 1 and enter the
corresponding parameter values into controller # 1.
If the sensor signal is connected to Analog Input 1, then enter the values into
parameters 43 and 44.
If the sensor signal is connected to Analog Input 2, then enter the values into
parameters 45 and 46.
Refer to page 17 for more information about setting these parameters.
Configure controller # 2 to output its sensor signal through one of its analog outputs
(set parameter 38 or 39).
Table 1
Sensor
Type
Sensor Model
Number
Sensing Area
Width
inches [mm]
Parameter
43 or 45
Parameter
44 or 46
PointSource
Ultrasonic
E/D
1.5x3U 4043-XX 0.20 [5] 0 20
3x3U 4050-XX 0.20 [5] 0 20
4x6U 4060-XX 0.20 [5] 0 20
4x12U 4090-XX 0.20 [5] 0 20
Ultrasonic
WideArray
E/D
1.5X3.75U 4612-XX 1.4 [36] 1 40
4x3.75U 4621-XX 1.4 [36] 1 40
1.5x5U 4511-XX 2.6 [66] 2 60
4x5U 4500-XX 2.6 [66] 2 60
1.5X9U 4524-XX 6.6 [168] 6 60
4x9U 4520-XX 6.6 [168] 6 60
4x14U 4530-XX 11.4 [290] 11 40
4x21U 4540-XX 18.6 [472] 18 60
Hi-Temp
Ultrasonic
E/D
UT 4068-XX 0.20 [5] 0 20
PointSource
Infrared
E/D
1.5x3L 4044-XX 0.20 [5] 0 20
3x3L 4051-XX 0.20 [5] 0 20
4x6L 4061-XX 0.20 [5] 0 20
4x12L 4091-XX 0.20 [5] 0 20
Infrared
WideArray
E/D
1.5x3.75L 4611-XX 1.4 [36] 1 40
4x3.75L 4620-XX 1.4 [36] 1 40
1.5x5L 4512-XX 2.6 [66] 2 60
4x5L 4501-XX 2.6 [66] 2 60