Instruction manual

MICRO 4000
®
NET Controller
49
Operation:
Discrete Isolated Outputs
Output
Connector
J10 terminal
Description
IN LIMIT
1
This output is on when the actuator has reached the In limit and is off
during normal operation. This output does not function if a MX-series
actuator is installed.
OUT LIMIT
2
This output is on when the actuator has reached the Out limit and is off
during normal operation. This output does not function if a MX-series
actuator is installed.
SERVO-CENTER
3
This output is on when the actuator is at the servo-center position and is
off during normal operation.
AUTO MODE
4
This output is on when the controller is operating in Automatic mode and
is off during all other modes of operation.
NO FAULT
5
This output is on when the controller is ready to operate and is off when
any of the following conditions occur:
The controller is displaying an error code. Refer to page 42 for more
information about error codes.
AC power is off.
An edge-loss or line-loss condition occurs. This option is enabled by
setting parameter 47. Refer to page 17 for more information about
setting controller parameters.
AUXILIARY
6
This output is controlled by parameter 58. Refer to page 17 for more
information about setting controller parameters.
7
This is the connector COMMON. For sourcing outputs, connect the +
customer supplied voltage. For sinking outputs, connect the - customer
supplied voltage.
MICRO 4000
®
NET Controller
49
Operation:
Discrete Isolated Outputs
Output
Connector
J10 terminal
Description
IN LIMIT
1
This output is on when the actuator has reached the In limit and is off
during normal operation. This output does not function if a MX-series
actuator is installed.
OUT LIMIT
2
This output is on when the actuator has reached the Out limit and is off
during normal operation. This output does not function if a MX-series
actuator is installed.
SERVO-CENTER
3
This output is on when the actuator is at the servo-center position and is
off during normal operation.
AUTO MODE
4
This output is on when the controller is operating in Automatic mode and
is off during all other modes of operation.
NO FAULT
5
This output is on when the controller is ready to operate and is off when
any of the following conditions occur:
The controller is displaying an error code. Refer to page 42 for more
information about error codes.
AC power is off.
An edge-loss or line-loss condition occurs. This option is enabled by
setting parameter 47. Refer to page 17 for more information about
setting controller parameters.
AUXILIARY
6
This output is controlled by parameter 58. Refer to page 17 for more
information about setting controller parameters.
7
This is the connector COMMON. For sourcing to the outputs, connect the
+ customer supplied voltage. For sinking from the outputs, connect the -
customer supplied voltage.