Instruction manual
MICRO 4000
®
 NET Controller 
25
Analog Output 1 
3 8          0 
  The output voltage is 0.0 volts. This is the default setting. 
3 8          1 
  The output voltage is proportional to the motor drive command signal.
The output voltage range is –10 to +10 volts. 
3 8          2 
  The output voltage is proportional to the signal read by Input A, Input B,
Input C or the centerline combination of Inputs A and B. The inputs are
selected by the front-panel switchpad, fieldbus, or Discrete Isolated 
Inputs. The output voltage range is –10 to +10 volts. 
3 8          3 
  Same function as option 2, except the output voltage range is 0 to +10
volts. 
3 8          4 
  The output voltage is proportional to the signal read by Input A. The 
output voltage range is –10 to +10 volts. 
3 8          5 
  Same function as option 4, except the output voltage range is 0 to +10
volts. 
3 8          6 
  The output voltage is proportional to the signal read by Input B. The
output voltage range is –10 to +10 volts. 
3 8          7 
  Same function as option 6, except the output voltage range is 0 to +10
volts. 
3 8          8 
  The output voltage is proportional to the web width. The remote station
sets the output voltage range. 
3 8          9 
  The output voltage is proportional to the voltage at Analog Input 1. The
output voltage range is -10 to +10 volts. 
3 8         1 0 
  Same function as option 9, except the output voltage range is 0 to +10
volts. 
3 8         1 1 
  The output voltage is proportional to the voltage at Analog Input 2. The
output voltage range is -10 to +10 volts. 
3 8         1 2 
  Same function as option 11, except the output voltage range is 0 to +10
volts. 
3 8         1 3 
  The output voltage is proportional to the guide point value. The outpu
t
voltage range is -10 to +10 volts. 
3 8         1 4 
  Same function as option 13, except the output voltage range is 0 to +10
volts. 
3 8         1 5 
  This option is used in resolving-centerline systems only. The output 
voltage drives the resolver’s controller. The output voltage range is -10 to 
+10 volts. 
3 8         1 6 
  Same function as option 15, except the output voltage range is 0 to +10
volts. 
[continued on next page] 