Instruction manual

MICRO 4000
®
NET Controller
25
Analog Output 1
3 8 0
The output voltage is 0.0 volts. This is the default setting.
3 8 1
The output voltage is proportional to the motor drive command signal.
The output voltage range is –10 to +10 volts.
3 8 2
The output voltage is proportional to the signal read by Input A, Input B,
Input C or the centerline combination of Inputs A and B. The inputs are
selected by the front-panel switchpad, fieldbus, or Discrete Isolated
Inputs. The output voltage range is –10 to +10 volts.
3 8 3
Same function as option 2, except the output voltage range is 0 to +10
volts.
3 8 4
The output voltage is proportional to the signal read by Input A. The
output voltage range is –10 to +10 volts.
3 8 5
Same function as option 4, except the output voltage range is 0 to +10
volts.
3 8 6
The output voltage is proportional to the signal read by Input B. The
output voltage range is –10 to +10 volts.
3 8 7
Same function as option 6, except the output voltage range is 0 to +10
volts.
3 8 8
The output voltage is proportional to the web width. The remote station
sets the output voltage range.
3 8 9
The output voltage is proportional to the voltage at Analog Input 1. The
output voltage range is -10 to +10 volts.
3 8 1 0
Same function as option 9, except the output voltage range is 0 to +10
volts.
3 8 1 1
The output voltage is proportional to the voltage at Analog Input 2. The
output voltage range is -10 to +10 volts.
3 8 1 2
Same function as option 11, except the output voltage range is 0 to +10
volts.
3 8 1 3
The output voltage is proportional to the guide point value. The outpu
t
voltage range is -10 to +10 volts.
3 8 1 4
Same function as option 13, except the output voltage range is 0 to +10
volts.
3 8 1 5
This option is used in resolving-centerline systems only. The output
voltage drives the resolver’s controller. The output voltage range is -10 to
+10 volts.
3 8 1 6
Same function as option 15, except the output voltage range is 0 to +10
volts.
[continued on next page]