Instruction manual
MICRO 4000
®
 NET Controller 
21
Edge Detector A Transmit Level 
1 6  a a. b b b 
  This parameter displays edge detector A’s transmit levels. Digits aa
display the beam number and digits bbb display the transmit level. Use 
the DATA buttons to select the desired beam. 
Edge Detector B Transmit Level 
1 7  a a. b b b 
  This parameter displays edge detector B’s transmit levels. Digits aa
display the beam number and digits bbb display the transmit level. Use 
the DATA buttons to select the desired beam. 
Minimum Deadband 
1 8          5 
 The minimum deadband is a zone around the sensor guide point that the 
web edge or line must enter before the motor drive is turned off. Once
the web edge or line position enters this zone, it must then move outside 
of the maximum deadband zone before the motor drive is turned on. The 
Minimum Deadband value must be lower than the Maximum Deadband
value. The default value is 5. 
Range: 0 to 100   
INHIBIT Input Mode 
Refer to page 45 for more information about the INHIBIT input. 
1 9          0 
  The actuator will run only if the INHIBIT input is activated. The INHIBIT
input controls the actuator in Automatic, Manual, or Servo-Center mode.
1 9          1 
  Same function as option 0, except the polarity of the INHIBIT input is
inverted. This is the default setting. 
1 9          2 
  The actuator will run only if the INHIBIT input is activated. The INHIBIT
input controls the actuator only in Automatic mode. 
1 9          3 
  Same function as option 2, except the polarity of the INHIBIT input is
inverted. 
Note: If your application requires an opto-isolated INHIBIT input, then set parameter 72 to 1. 
Calibrate Edge Detector A 
2 0          0 
  This parameter initiates the calibration of edge detector A. Refer to page
59 for calibration instructions. 
Range: 0 to 2   
Calibrate Edge Detector B 
2 1          0 
  This parameter initiates the calibration of edge detector B. Refer to page 
59 for calibration instructions. 
Range: 0 to 2   