Instruction manual
Fieldbus Interface
113
Input Array byte 1 Operating Mode Status
Bit Function Value Status Indicated
7 Auto
1
Parameter 51 (Switchpad Type) is set to 0 or 1:
Not defined.
Parameter 51 (Switchpad Type) is set to 2:
The unit is in Automatic mode.
0 This mode not selected.
6
Servo
Center
1 The unit is in Servo-Center mode.
0 This mode not selected.
5 Manual
1 The unit is in Manual mode.
0 This mode not selected.
4 In
1 The unit is in Manual mode and the In command is active.
0 This mode not selected.
3 Out
1 The unit is in Manual mode and the Out command is active.
0 This mode not selected.
2 Input A
1
Parameter 51 (Switchpad Type) is set to 0 or 1:
Input A is selected and the unit is in Automatic mode.
Parameter 51 (Switchpad Type) is set to 2:
Input A is selected.
Note: If the Input A and B status bits are both set to 1, then the unit is
in Centerline mode.
0 This mode not selected.
1 Input B
1
Parameter 51 (Switchpad Type) is set to 0 or 1:
Input B is selected and the unit is in Automatic mode.
Parameter 51 (Switchpad Type) is set to 2:
Input B is selected.
Note: If the Input A and B status bits are both set to 1, then the unit is
in Centerline mode.
0 This mode not selected.