Instruction manual
Fieldbus Interface 
112
Input Array data format – detailed description: 
Input Array byte 0 Actuator Status 
Bit  Function  Value  Status Indicated 
7  In Limit 
1  The actuator has retracted to the In limit position. 
0  The actuator is not at the In limit position. 
6  Out Limit 
1  The actuator has extended to the Out limit position. 
0  The actuator is not at the Out limit position. 
5 
Servo 
Center 
1  The actuator has reached the Servo-Center position. 
0  The actuator is not at the Servo-Center position. 
4  not used  x  none 
3  No Fault 
1  The controller is operating correctly. There are no operating faults. 
0 
The controller is not operating correctly. Check the flashing ‘99’ error 
code on the controller’s parameter-entry display. Refer to page 42 for 
more information about error codes. 
or
An edge-loss or line-loss condition has occurred. This option is 
enabled by setting parameter 47. Refer to page 17 for more 
information about setting controller parameters. 
2  not used  x  none 
1  not used  x  none 
0  not used  x  none 