Instruction manual

Fieldbus Interface
107
Output Array data format – detailed description:
Output Array bytes 0 and 1 Operating Mode Command
Byte Bit Function Value
Switchpad
Type
(Param 51)
Action Performed
0
7 Auto
1
0 or 1 No change.
2
Select Automatic mode (guide the web using position
feedback from sensors selected by the Input A, B, C, or
Centerline command bits).
0 x No change.
6
Servo
Center
1 x
Select Servo-Center mode (move actuator to Servo-Center
position).
0 x No change.
5 Manual
1 x Select Manual mode (stop actuator).
0 x No change.
4 In
1 x Select Manual mode and In mode (move actuator in).
0 x No change.
3 Out
1 x Select Manual mode and Out mode (move actuator out).
0 x No change.
2 Input A
1
0
Select Input A and Automatic mode.
Note: To select Centerline mode, set the Input A and B
command bits to 0 and the Centerline command bit to 1.
1
Select Input A and Automatic mode.
Note: To select Centerline mode, set the Input A and B
command bits to 1 and the Input C command bit to 0.
2
Select Input A.
Note: To select Centerline mode, set the Input A and B
command bits to 1 and the Input C command bit to 0.
0 x No change.