User manual
Publication 2092-UM001D-EN-P — July 2005
B-2 Interconnect and Cable Diagrams
Power Connections
Figure B.1 shows the recommended power wiring for a typical Ultra1500 drive 
and motor system.
Figure B.1
Ultra1500 Simplifier Power Wiring Diagram 
L1 
ULTRA1500
L2 
L3 
L1C 
L2C 
N 
P1 
P2 
B1 
B2 
M1 
AC 
LINE 
FILTER
SHUNT 
RESISTOR 
U 
V 
W 
MOTOR 
FUSE 
BLOCK 
1:1 ISOLATION 
TRANSFORMER 
GROUND BAR 
1 
1 
2 
3 
4 4 
FUSED 
DISCONNECT 
OR CIRCUIT 
BREAKER 
230V 
3-PHASE 
AC LINE 
50/60 HZ 
TO 
ADDITIONAL 
DRIVES 
NOTES: 
1.  HIGH-FREQUENCY GROUNDING USING HEAVY BRAIDS SHOULD CONNECT TOGETHER THE ELECTRONIC EQUIPMENT, THE ELECTRICAL ENCLOSURE, THE 
MACHINE FRAME AND THE MOTOR HOUSING. 
2.  THE INTERNAL SHUNT RESISTOR IS ONLY PRESENT ON THE 2092-DA3, 2092-DA4, AND 2092-DA5 MODELS. B1 AND B2 SHOULD BE LEFT DISCONNECTED ON 
THE 2092-DA1 AND 2092-DA2 MODELS. 
3.  AN ISOLATION TRANSFORMER IS OPTIONAL. IF USED, THE SECONDARY OF THE TRANSFORMER MUST BE GROUNDED. 
4.  THE 2092-DA1 AND 2092-DA2 MODELS HAVE ONE GROUNDING SCREW ON THE HEATSINK, AND THE 2092-DA3, 2092-DA4, AND 2092-DA5 MODELS HAVE TWO 
GROUNDING SCREWS ON THE HEATSINK. 
5.  THE 2092-DA1, 2092-DA2, AND 2092-DA3 MODELS ARE SINGLE-PHASE AC INPUT, AND L3 SHOULD BE LEFT DISCONNECTED. 
6.  THE JUMPER FROM P1 TO P2 CAN BE REPLACED WITH AN INDUCTOR, IF THE POWER FACTOR OR HARMONIC DISTORTION NEEDS IMPROVEMENT. 
5 
CASE 
6 