User manual
Publication 2092-UM001D-EN-P — July 2005
A-4 Specifications and Dimensions
Fuse and Contactor Specifications
Use class CC, J, or R class fuses, with current ratings as indicated in the table 
below. The table below lists fuse examples recommended for use with the 
Ultra1500 drives.
Refer to Power Wiring Requirements in Chapter 3 for input wire size.
1 For contactors, x represents coil voltage, and y represents number of contacts. 
Power Dissipation Specifications
Use the following table to size an enclosure and calculate required ventilation 
for the Ultra1500. Typical heat losses run approximately one-half maximum 
power losses. The maximum power losses are shown below. 
Catalog Number Input Type
Input 
Voltage
Recommended Bussmann
®
 Fuse
Recommended 
Allen-Bradley 
Contactor 
1
Class CC  Class J  Class RK5
2092-DA1 
Main Input Power
230V, 1φ
FNQ-R-7 
N/A
N/A
100-M05Nxy 
2092-DA2 100-M09Nxy 
2092-DA3 FNQ-R-10 100-M12Nxy 
2092-DA4
230V, 3φ
FNQ-R-15 LPJ-15  100-C16xy 
2092-DA5 FNQ-R-20 LPJ-20  100-C23xy 
2092-DA1, 2092-DA2, 
2092-DA3, 2092-DA4, 
and 2092-DA5
Control Input Power 230V, 1φ FNQ-R-7-1/2 LPJ-6  FRS-R-2-1/2 N/A 
Catalog Number
Maximum Loss
Watts
2092-DA1 50 
2092-DA2 50
2092-DA3 50 + dissipative shunt
2092-DA4 100 + dissipative shunt
2092-DA5 150 + dissipative shunt