FEATURES
• Insulation Resistance 2.0GΩ
• Earth-bond Resistance 20.00kΩ
• True RMS
• 1000V AC/DC
• Resistance 40MΩ
• Capacitance 10,000μF
• Frequency 99.99kHz
• Continuity and Diode test
• mAmps
• Temperature: -328˚ to 2462˚F (-200˚ to 1350˚C)
• PI/DAR test
• A-Hold/ Hold
• Zero reading
• Lock reading
• Rotary style selector
• Protective rubber boot
• Kick stand
• Test lead holders
• Remote probe
• Auto power off
• Backlit Display
• Worklight
GENERAL SPECIFICATIONS
• Operating Temperature: 32˚ to 122˚F (0˚ to 50˚C)
• Storage Temperature: 14˚ to 122˚F (-10˚ to 50˚C)
• Operating Humidity: <75%
• Operating Altitude: 6,526 ft (2000m)
• Pollution Degree: 2
• Over range: “OFL” is displayed
• Backlight: Yes
• Refresh Rate: 3/sec
• Dimensions: 8.27” x 3.52” x 2.17”
• Item Weight: 1.283 lbs
• Calibration: Recommended annually
• CAT Rating: CATIV 600V/ CATIII 1000V
• Certifications: CATIV 600V/CATIII 1000V, cETLus 3rd Edition, CE Conformity, IP42, RoHS,
IEC/EN61010-1: 2010, 6’ Drop Protection
• Battery Type: (AA) 4
• Test Leads: Silicone test leads w/ alligator clips (red and black) (ATL57), Remote Probe
• Accuracy: ± (% of reading + # of least significant digits)
• Bargraph: 30 segment
IRT807 Insulation resistance tester is designed to help prevent hazards such as electric shock and short-circuits
caused when the insulation in electrical devices, parts, and equipment used in plants, buildings, and other settings
degrades over long periods of use.