User Guide

Continuity
Buzzer sounds at less than 40Ω.
WARNING
Do not measure resistance on a live circuit.
Features:
HOLD
Continuity
Audible threshold Response time Overload Protection
Approx : < 40Ω 50ms 600V
CAT III
600V
V
Ω
DL200
600V CAT III 200A
HOLD
Single
Conductor
Only
AC Amps: <200A
CAT III
600V
V
Ω
DL200
600V CAT III 200A
Center wire in conductor alignment marks for best accuracy.
Opposing currents cancel (use line-splitter when necessary).
WARNING
Keep hands below guard when measuring high current levels.
Do not attempt to measure more than 200A AC.
Features:
HOLD
AC Amps – Jaw Input
Ranges Resolution Accuracy Overload Protection
1A to 200A 0.1A ±(2.0% + 5 dgts) 600V
Frequency Range: sine wave: 45Hz to 400Hz
Maximum Displayed value: AC220A
Minimum Displayed value: AC 500mA
CAT III
600V
V
Ω
DL200
600V CAT III 200A
HOLD
Test Lead Notes
CATIV 600V Measurement Locations
The DL200 is CATIII rated to IEC 61010-1 3rd edition standards. Do not
attempt to measure in locations that requires a CATIV rated meter. Remove
the CATIV test lead caps and use the CATIII 1000V test lead measurement
locations.
CATIII 1000V Measurement Locations
CATIV shields must be removed for CATII and CATIII locations.