MEASURING AIR VOLUME CONT.
We recommend the following number of access holes depending on duct
size;
• 18”orless–Twoaccessholes6”apart
• 18”~30”–Fiveaccessholes
• 30”~36”–Sixaccessholes
• Greaterthan36”–Sevenaccessholes
ACCESS HOLE SPACING
Use the Log-Tchebycheff Rule for rectangular ducts to determine spacing
for access holes.
Number of access
holes per side
Position relative to inner wall
(multiplier)
5 0.074, 0.288, 0.500, 0.712, 0.926
6 0.061, 0.235, 0.437, 0.563, 0.765, 0.939
7 0.019, 0.153, 0.217, 0.361, 0.639, 0.783,
0.847, 0.923, 0.981
Example–fora20”insidedimensionselect5accessholes.
• Access1,20x0.074=1.48”fromwall(use1½“)
• Access2,20x0.288=5.76”fromwall(use5¾”)
• Access3,20x0.500=10”fromwall(use10“)
• Access4,20x0.712=14.24”fromwall(use14¼“)
• Access5,20x0.926=18.52”fromwall(use18½“)
SAMPLE CALCULATED LOCATIONS
Access
Holes
5 Access
Holes
6 Access
Holes
7
Width 24 Width 30 Width 36
0.074 1.8 0.061 1.8 0.053 1.9
0.288 6.9 0.235 7.1 0.203 7.3
0.500 12.0 0.437 13.1 0.366 13.2
0.712 17.1 0.563 16.9 0.500 18.0
0.926 22.2 0.765 23.0 0.634 22.8
0.939 28.2 0.797 28.7
0.947 34.1