Owner manual
6
atmoSpheriC gaS fired burNerS
• CO2 ...................................................................................7.0to8.0%CO2
• Stack Temperature .........................................................325to500°F
• Draft (WaterColumnInches) ..........................................-.02to-.04wc”
• Carbon Monoxide(partspermillion) ............................<100ppm
gaS fired power burNerS
• CO2 ...................................................................................6.0to7.0%CO2
• Stack Temperature .........................................................275to500°F
• Stack Draft (WaterColumnInches) ...............................-.02to-.04wc”
• Overfire Draft (WaterColumnInches) ..........................-.02wc”
• Carbon Monoxide(partspermillion) ............................<100ppm
oil fired burNerS (#2 oil fuel)
• CO2 ...................................................................................6.6to8.0%CO2
• Stack Temperature .........................................................325to600°F
• Stack Draft (WaterColumnInches) ...............................-.04to-.06wc”
• Overfire Draft (WaterColumnInches) ..........................-.02wc”
• Carbon Monoxide(partspermillion) ............................<100ppm
• Smoke ..............................................................................0
(ormanufacturer’srecommendation)
poSitive overfire gaS & oil
• CO2 ...................................................................................5.8to10.3%CO2
• Stack Draft (WaterColumnInches) ...............................-.02to-.04wc”
• Overfire Draft (WaterColumnInches) ..........................+0.4to+0.6wc”
• Carbon Monoxide(partspermillion) ............................<100ppm
NOTE: Followmanufactureguidelinesforthespecificequipmentbeingserviced.
- Temperature and draft targets are included for reference only.
TheC20doesnotmeasuretheseparameters
WHAT RESULTS ARE GENERALLY ACCEPTABLE