Each active alarm can be set to send an SNMP trap, mute the modulator output, as well
as trigger one or both alarm relays, if desired.
The integration time can be set to any value between 0 to 360 seconds. This parameter
allows the modulator to avoid reporting intermittent alarms. Any alarm will be reported
only if it is still active after the integration time has elapsed.
For each alarm the user can set the following:
Item Selection
Trap notification on Alarm OFF, ON
Set as ON/OFF to control if an alarm will produce a SNMP
trap notification
Integration Time Range: 0 .. 360 sec
Length of time an alarm condition is present before the
alarm is declared
Mute on Alarm OFF, ON
Set to control whether the modulator output is muted for
this alarm
Relay on Alarm OFF, ON
Set to control whether the alarm relay is activated with
this alarm
Second Relay on Alarm OFF, ON
Set to control whether the second alarm relay is
activated with this alarm
Table 16: Alarm Properties
Clear Logs
The alarm logs can be cleared by setting the Clear Log pull down box to ”Yes” and
selecting Submit.
Figure 25: Clear Logs Page