Assembly Instructions Chapter 3

10-kW UHF Transmitter with Chapter 3, Installation and
Feedforward Drive Setup Procedures
840A, Rev. 0 3-1
Chapter 3
Installation and Setup Procedures
There are special considerations that
need to be taken into account before the
840A can be installed. For example, if the
installation is completed during cool
weather, a heat-related problem may not
surface for many months, suddenly
appearing during the heat of summer.
This section provides planning
information for the installation and set up
of the transmitter.
3.1 Site Considerations
The 840A transmitter requires two main
AC input lines, a 3-phase 208/240 VAC,
60 Hz input of at least 100 amp rating
that connects to the high-voltage power
supply assembly and a single-phase
208/240 VAC, 60 Hz input of at least 40
amp rating that connects to the
exciter/driver assembly. Make sure that
the proposed site has the necessary
voltage requirements.
The cabinets should be positioned with
consideration given for adequate air
intake and exhaust. In addition,
installation planning should take into
account the amount of space required for
the opening of the front of the metering
control panel on the 10-kW amplifier; the
opening of the rear doors on the 10-kW
amplifier and exciter/driver cabinets;
access to the trays, including sliding
them out for testing; the main AC hook-
up to the high-voltage power supply
assembly; and the installation of the
output transmission line, including the
trap filters and the directional coupler.
The 10-kW amplifier cabinet contains a
tube cavity air exhaust stack that is a
10.5-inch chimney mounted on the roof
of the cabinet. Forced air flows though
this chimney from the blower assembly
that cools the tube mounted in the cavity
assembly (1,100 CFM at 30° C rise).
The 10-kW amplifier cabinet also has two
exhaust fans, rated at 240 CFM, mounted
in the top cover assembly of the cabinet.
Air intake for the tube cavity blower
assembly is through the large filter
mounted on the bottom rear of the
cabinet.
The high-voltage power supply cabinet
has two exhaust fans, each rated at 550
CFM, mounted in the top cover assembly
of the cabinet. Air intake for the cabinet
is through the two filters mounted on
each side of the cabinet.
The 840A is designed and built to provide
long life with a minimum of maintenance.
The environment in which it is placed is
important and certain precautions must
be taken. The three greatest dangers to
the transmitter are heat, dirt, and
moisture. Heat is usually the greatest
problem, followed by dirt, and then
moisture. Over-temperature can cause
heat-related problems such as thermal
runaway and component failure. Each
amplifier tray in the transmitter contains
a thermal interlock protection circuit that
will shut down that tray until the
temperature drops to an acceptable level.
A suitable environment for the
transmitter can enhance the overall
performance and reliability of the
transmitter and maximize revenues by
minimizing down time. A properly
designed facility will have an adequate
supply of cool, clean air, free of airborne
particulates of any kind, and no
excessive humidity. An ideal environment
will require temperature in the range of
40° F to 70° F throughout the year,
reasonably low humidity, and a dust-free
room. It should be noted that this is
rarely if ever attainable in the real world.
However, the closer the environment is
to this design, the greater the operating
capacity of the transmitter.

Summary of content (14 pages)