Assembly Instructions

835A 4 kW, 5 kW or 6 kW UHF Transmitter Site Considerations
- Page 3 of 3 -
In calculating the blower requirements, filter size and exhaust size, use the following guide. If the total load is known in Watts,
you will need 2000 CFM into 1/2" of water for each 5000 Watts. If the load is known in BTU's you will need 2000 CFM into
1/2" of water for each 17,000 BTU's. The inlet filter must be seven square feet minimum, larger for dusty and remote
locations, for each 5000 Watts or 17,000 BTU's. The exhaust must be at least four square feet at the exhaust screen for each
5000 Watts or 17,000 BTU's. The above is a general guide and may need modified for unusually severe conditions.
A combination of air conditioning and ventilation installation should not be difficult to design using the above information.
System interlocking and thermostat settings should be reviewed with Axcera. As with any equipment installation it is always
good practice to consult the manufacturer when questions arise. Axcera may be contacted at (724) 873-8100.