Datasheet
ORDER CODE: State part number: QLC 230V AC
Optional extras include: heatsink paste, filter.
Note: When ordering a filter the maximum current the QLC is to be used at will be required
CE MARKING
This family carries a “CE” marking. These phase angle controllers need a suitable remote filter. For more information see
recommendations section and contact our sales desk. (See Declaration of Conformity)
FUSING
It is recommended to use semiconductor (fast-acting) type fuses or circuit breakers (semiconductor-MCB) for protection. On
initial use some loads may need an increased factor of safety for unit and/or device protection (see SRA datasheet for further
information).
INSTALLATION
RECOMMENDATIONS
Other documents are available on request, which may be appropriate for your application: -
CODE IDENTITY DESCRIPTION
X10229 RFI Single-phase filtering recommendations - addressing EMC Directive
X10213 ITA Interaction, uses for phase angle and for burst fire control.
X10255 SRA Safety requirements - addressing the Low Voltage Directive
(LVD) including: - thermal data/cooling; live parts warning and earth
requirements; fusing recommendations.
P01.1 COS UAL Conditions of sale.
NOTE: It is recommended that installation and maintenance of this equipment should be done with reference to the current
edition of the I.E.T. (formally I.E.E.) regulations (BS7671) by suitably qualified/trained personnel. The regulations contain
important requirements regarding installation and safety of electrical equipment. Specific installers should refer to local and
national regulations.
SPECIFICATIONS
Triac limiting rms on state current 26A Isolation voltage 2500V rms
Unit limiting rms on state current 15A I
2
t limiting value for fusing 112A
2
s
Peak single cycle surge @ 10mS 320A Mains supply ( within 10%) 230V ac @ 50/60 Hz
Max load at 20ºC ambient
(without extra heatsink)
10A min operating current 200mA
Max unit operating temperature 65ºC Unit storage temperature range -20 to +85ºC
FURTHER DIMENSIONS
Shaft diameter 6.3mm Shaft projection from bush 30mm
Bush length 5mm Standard cable length 400mm
UNITED AUTOMATION LIMITED
Southport Business Park Tel: 0044 (0) 1704 – 516500
Wight Moss Way Fax: 0044 (0) 1704 – 516501
Southport, PR8 4HQ enquiries@united-automation.com
ENGLAND www.united-automation.com
Page No. 2 of 2 Issue 3 Date 31/07/12