Datasheet

ORDER CODE
:
State part number:
CSR1 or 2
(
Denotes supply voltage
) + (
current rating
) +
type
B’
or
‘E’
Optional extras include: Knob, Dial, Heatsink compound, Filters.
Note: When ordering a filter, the current the CSR is to be used at will be required.
RECOMMENDATIONS
Other documents available on request, which may be appropriate for your applications:-
CODE
IDENTITY
DESCRIPTION
X10229
RFI
Filtering recommendation -
addressing EMC Directive.
X10213
ITA
Interaction, uses for phase angle and for burst fire control.
X10255
SRA
Safety requirements - addressing the Low Voltage Directive (LVD) including :-
Thermal data/cooling ; “Live” parts warning & Earth requireme
nts; Fusing
recommendations.
AP02/4
COS
UAL Conditions of sale.
NOTE
It is recommended that installation and maintenance of this equipment should be done with reference to the current
edition of the I.E.E. wiring regulations (BS7671) by suitably qualified/trained personnel. The regulations contain
important requirements regarding safety of electrical equipment.
(For International Standard refer to I.E.C. directive IEC 950).
CE MARKING
This product family carries a “CE marking”. These phase angle controllers need a suitable remote filter. For more
information see
recommendations
section and contact our sales desk.
FUSING
It is recommended to use semiconductor (fast acting) type fuses or circuit breakers (semiconductor- MCB) for unit protection.
On initial ‘switch on’ some loads may need an increased Factor of Safety (F of S) for unit and/or device protection. See SRA
Data sheet for further information.
INSTALLATIONS
COOLING REQUIREMENTS
Heatsink rating v RMS maximum current
SPECIFICATIONS
UNIT
CSR1 (110V) & CSR2 (230V)
TYPE
6B 6E 10B 10E 15B 15E
Maximum on-state current, I
max
(tab @70ºC)
A (
RMS
) 6 6 10 10 15 15
Peak one cycle surge currents
A 100 100 120 120 150 150
Off - leakage current (maximum)
mA
------------------------------------- 2 ----------------------------------
Minimum holding load current
mA
---------------------------------------30 ----------------------------------
RMS input voltage +/- 10% @ 50/60 Hz
V
Repetitive peak voltage (tab @ 70ºC)
V
------------------------------------ 400 ---------------------------------
Hysteresis
%
--------------------------------------- 5 ----------------------------------
Total conduction phase angle (typical)
degrees
---------------------------------- 0 to 160
---------------------------
Controlled phase angle (typical)
degrees
--------------------------------- 30 to 160
---------------------------
Power transfer at I
max
(efficiency)
%
------------------------------------- 99 ----------------------------------
Tab surface operating range
ºC
----------------------------------- 0 to + 75 ----------------------------
Storage temperature
ºC
----------------------------------- 0 to + 75 --------------------------
Insulation withstand capability (tab @ 70ºC)
V
--------------------------------- 1500 for 1 min. -----------------------
I
2
t limiting values for fusing
A
2
s 18 18 50 50 100 100
Mounting hole diameter (minimum)
mm
10.3
10.3
10.3
10.3
10.3
10.3