Technical data
PD_OpManPS-4_05_us.fm
page 32  PacDrive PS-4 / PD-8 ELAU AG
5 Maintenance
Hard-copy for correction
Commissioning procedure:
Unpacking and
checking
 Remove packaging.
 Make sure the units are not damaged. Only undamaged units 
should be put into operation. 
 Check if the consignment is complete.
 Check the data with the help of the type plate.
See also "Unpacking" on page 21.
See also "Exchanging units" on page 27.
Setting the
SERCOS
address
 Set the intended SERCOS address (0-99) with a suitable tool.
NOTE
Make sure no address is used twice in a SERCOS ring! Each 
SERCOS slave needs its own, unambiguous SERCOS address.
Installation  Observe the requirements for the place in which the equipment 
may be used.
 Observe the requirements for protection and EMC rules.
CAUTION!
PacDrive PS-4 has a rated connection voltage of 230 V! 
Incorrect connection voltage may result in the destruction of the 
device!
When using the devi8ce in rotary current networks (3 AC 380...480 
V), use an autotransformer to avoid a destruction of the PS-4.
 Mount the device.
Fig. 5-1: Assignment for connections to PS-4
PD_Inb_PS-4_1_us.fh8
DC+
DC-
PE
24V
0V
4
5
3
1
2
4
5
3
1
2
5 / 6
7 / 8
1
2
X1
X2
X3
X4
X8
X6
X5
+24V
0V
PE
L1
L2
L3
DC+
DC+
DC-
DC-
24V
0V
PE
DC+
DC-
SERCOS
HW enable
0V
ZK dis
0V
LWL in
LWL out
RDY+
RDY -
NC
NC
 ! 230V !
1
2
3
4
5
1
2
3
4
1
2
3
4
5
6
1
2
3
4
5
6
7
8
PS-4 Front
connecting cable PS-4/PD-8
0
2
3
4
5
6
1
7
8
9
0
2
3
4
5
6
1
7
8
9
S1
S2
SERCOS
address switch
tens digit
units digit
L1 L2 L3 PE
3~
24V=
K1
power supply
connection, 3 phase
Q2
Q1
autotransformer optional;
required, if U
Netz
 = 230 V