5.7 Commissioning
Hard-copy for correction
CAUTION!
Electromagnetic fields!
Disturbances or failure of the system possible!
The rules described below must be observed for installation, in 
order to rule out the consequences of excessive disturbance effects 
as far as possible.
In correlation with electronic controls, no inductive loads must be 
switched without suitable interference elimination.
 For DC operation, suitable interference elimination can be 
achieved by arranging recovery diodes. For AC operation, 
commercially available erasing elements matching the 
connector type can be used.
 Only the interference elimination element mounted immediately 
at the point of inductivity serves its purpose. Otherwise, the 
switching pulse may even emit increased interference via the 
interference elimination elements. It is much easier to avoid 
sources of interference in the first place, than to eliminate the 
effects of existing interference.
 In no case must the contacts switching unerased inductive loads 
be arranged in the same room as the PacDrive™ components. 
The same goes for cables carrying unerased, switched 
inductivity and cables running parallel to them. The controller 
must be separated from such "disturbers" by a Faraday cage 
(own section in the switching cabinet).
5.7  Commissioning
We urgently recommend that you use ELAU staff for 
commissioning. 
You should do so not only for warranty reasons. At the same time
 the equipment is checked,
 the optimum configuration is determined,
 and the operating staff are instructed.
DANGER!
High leakage current!
Life hazard!
 The leakage current is greater than 3.5 mA. Therefore the units 
must have a firm connection to the power grid (according to DIN 
EN 50178 - equipment of high-voltage systems).