Specifications
48
b. Air leaking into oil line causing fl ame out.
c. Defective nozzle causing fl ame to be erratic.
d. Excessive airfl ow or draft causing fl ame to leave
burner head.
e. Excessive back pressure causing fl ame to be
erratic.
3. Control locks out after Trial For Ignition (TFI).
a. No oil to burner.
b. Shorted electrodes.
c. Nozzle clogged.
d. Airfl ow too high.
e. Ignitor module defective.
f. CAD cell defective.
g. Oil valve stuck open or closed.
Note: The Safety Monitoring Circuit (SMC) is
designed to provide lockout in the event of a
stuck or welded motor relay.