Specifications
26
A.  CHIMNEY VENTING 
1.  Chimney venting is an important part of a safe 
and effi cient oil fi red appliance system. Contact 
your local fi re and building offi cials on specifi c 
requirements for restrictions and the installation 
of fuel oil burning equipment. In addition, 
consult with a professional knowledgeable on 
the requirements of NFPA 31 – Standard for the 
Installation of Oil-Burning Equipment and NFPA 
211 - Standard for Chimneys, Fireplaces, Vents, and 
Solid Fuel-Burning Appliances for installations in 
the United States. Installations in Canada must be 
reviewed with a professional knowledgeable on the 
requirements of CSA B139-04 – Installation Code 
for Oil-burning Equipment. 
2.  The safe venting of oil fi red boilers is dependant on 
many factors. Some of these factors include:
a. suffi cient draft during the entire heating season 
to allow for the safe discharge of combustion by-
products and;
b.  suitable corrosion protection in the event of 
condensing fl ue gases. Only a trained and 
qualifi ed contractor may install this product.
3.  The MPO can be vented into a fi reclay tile-lined 
masonry chimney that meets requirements outlined 
in Paragraph 4 below. It can also be vented into 
a chimney constructed from type L vent or a 
factory built chimney that complies with the type 
HT requirements of UL 103. The chimney and 
vent pipe shall have a suffi cient draft at all times, 
to assure safe proper operation of the boiler. See 
Figure 16 for recommended installation.
GNINRAW
erifoteruliaF.ecnailppaehtetar-edtonoD
esuacyamtupnidengiseds'titatinueht
roiretniehtnopunoitasnednocev
issecxe
rewoleht,noitiddanI.yenmihcehtfosllaw
ottfardhguoneetaerctonyamtupni
fostcudorp-ybehtetaucaveyletauqeda
.noitsubmoc
4.  Chimney Inspection – Prior to the installation of 
any new or replacement fuel burning equipment the 
chimney shall be inspected by a qualifi ed installer. 
The chimney shall be inspected for integrity as 
well as for proper draft and condensate control. 
Some jurisdictions require the use of a liner when 
changing fuel types. Some jurisdictions require 
the use of a liner even when the same fuel is used. 
At a minimum, the chimney shall be examined 
by a qualifi ed person in accordance with the 
requirements of Chapter 11 of NFPA 211, Standard 
for Chimneys, Fireplaces, Vents, and Solid Fuel-
Burning Appliances.
SECTION V: VENTING 
a.  Loose Mortar – Loose mortar could be an 
indication of a prior history of condensing fl ue 
gases upon the inside walls of the chimney. 
Colder climates are more susceptible to this 
condition. Under no circumstances shall a 
chimney of this condition be used until it meets 
the requirements of NFPA 211 or CSA B139-
04.
b. Unlined Chimney – Under no circumstances 
shall a chimney constructed of brick only 
be used. Only approved clay liners or listed 
chimney lining systems shall be used as specifi ed 
in NFPA 31 or CSA B139-04.
c.  Abandoned Openings – Openings through the 
chimney wall that are no longer used shall 
be sealed in accordance to NFPA 211. Often 
abandoned openings are improperly sealed and 
usually covered by a gypsum wall covering.
d.  Clean Chimney – Chimney shall be free of all 
loose debris.
5.  Draft Regulator – the draft regulator supplied with 
the boiler must be used with this appliance. No 
other draft regulator shall be used. Refer to Figures 
16 and 17.
B.  CHIMNEY CONNECTOR
1.  A chimney connector (vent pipe) is used to connect 
the boiler to the base of the chimney. The chimney 
connector should be kept as short as possible. The 
horizontal length of the chimney connector shall not 
be greater than 10 feet.
  NOTE: Secure chimney connector to cast iron 
smokebox collar with three (3) #10 x ½" self drilling 
hex head TEK screws provided in miscellaneous 
parts carton. Locate screws around perimeter of 
connector as shown in Figure 16 and approximately 
½" in from edge. Use drill with 5/16" hex bit to 
drive screws through connector and smokebox 
collar.
REGNAD
ebllahsrotcennocdnayenmihcehT
dnasirbedfosngisrofyllaunnadetcepsni
ehtfoesabehttaratromesooL.noisorroc
etasnednocfongisaebyamyenmihc
yenmihcA.yenmihcehtotegamad
yletaidemmidetcatnocebllahslanoisseforp
adnemmocerdnaegamadehtenimaxeot
sihtnielihwnoitarepomretgnoL.noitulos
dnaeruliafgnitnevaesuacyamnoitidnoc
ehtfI
.ecapsgnivilehtotnisesageulfecrof
ehtesudenil-erebotsiyenmihc
ExidneppA,13APFNnisnoitadnemmocer
.40-931BASCro