  A 24 VAC LWCO is used primarily for gas red 
boilers where a 24 volt control circuit exists within the 
boiler. However, a 24 VAC LWCO can only be used 
if the boiler manufacturer has provided piping and 
wiring connections and instructions to allow for this 
application.
APPENDIX A - LOW WATER CUT OFF (LWCO) (continued)
How to Test
Shut off fuel supply. Lower water level until water 
level is BELOW the LWCO. Generate a boiler demand 
by turning up thermostat. Boiler should not attempt to 
operate. Increase the water level by lling the system. 
The boiler should attempt to operate once the water 
level is above the LWCO.