Instruction manual
61
SECTION XII: OPERATING (CONTINUED)
c. Low Limit (LL_)
  The Warm Start Boiler Control is factory 
programmed with a Low Limit Setpoint of 
110°F. On falling temperature the boiler 
turns “on” and the “ZC” terminal and System 
Circulator outputs are de-energized when the 
boiler temperature is less than the Low Limit 
Setpoint less the differential. On a rising 
temperature when the boiler temperature is above 
the Low Limit Setpoint the boiler turns “off”, 
the “ZC” terminal output is energized and the 
System circulator is enabled to respond to a call 
for heat. The Low Limit Setpoint is adjustable 
between 110°F and 220°F.
d. Low Limit Differential (Ldf)
  The Warm Start Boiler Control is factory 
programmed with a Low Limit Differential 
Setpoint of 10°F. The Low Limit Differential 
is the number of degrees the boiler temperature 
must decrease below the Low Limit Setpoint 
before the Warm Start Boiler Control takes 
actions to warm the boiler. These actions include 
starting the burner and stopping water ow 
through the boiler. The Low Limit Differential is 
adjustable between 10°F and 25°F.
e.  Circulator Overrun Time (OR_)
  Circulator Overrun Time (also called “circulator 
off delay” or “circulator post purge”) continues 
circulator operation after a call for heat has 
ended, sending excess heat from the boiler into 
the priority zone. Ensure system piping and zone 
panel settings allow water ow to the priority 
zone after the call for heat ends. The Circulator 
Overrun Time has a factor setting of 0 minutes 
and is eld adjustable between 0 and 10 minutes.
f.  Circulator Pre-Purge Time (PP_)
  When the boiler is warm [boiler water 
temperature higher than 140°F (adjustable using 
Start Temperature parameter)] and there is a 
thermostat call for heat, the system circulator 
is started and boiler ring is delayed pre-purge 
minutes. If the temperature drops below 140°F or 
there is a DHW Call for Heat the boiler is started 
without delay. Additionally, the boiler is started 
without delay if the thermostat call for heat is 
initiated when the boiler water temperature is 
less than 140°F. This feature helps save energy 
by satisfying home heating needs with residual 
boiler heat rather than cycling the boiler. The 
Circulator Pre-purge time has a factory setting of 
2 minutes and is eld adjustable between 2 and 
20 minutes. Refer to Table 6.
  The Warm Start Boiler Control Pre-purge Time is 
factor set to 0 minutes.
Cold Start Boiler Control
Adjustment Mode Options
HL_ 140-240°F Adjust High Limit Setting
HdF 10-30°F Adjust High Limit Differential
ZC_ dh, ZR or ELL ZC and ZR Terminal Function
Or_ 0-10 minutes Pump Overrun Time
PP_ 2-20 minutes Pump Pre-purge Time
t_ 140 - 180°F Start Temperature
Pt_ On or Off Priority Time
f-C F or C Select degrees F or C Mode
bac Back to Operating Mode
Warm Start Boiler Control
Adjustment Mode Options
HL_ 140-240°F Adjust High Limit Setting
LL_ 110-220°F Adjust Low Limit Setting
Ldf 10-25°F 
Adjust Low Limit Differential 
Setting
ZC_ ZR or dh ZC and ZR Terminal Function
Or_ 0-10 minutes Pump Overrun Time
PP_ 0-20 minutes Pump Pre-purge Time
t_ 140 - 180°F Start Temperature
Pt_ On or Off Priority Time
f-C F or C Select degrees F or C Mode
bac Back to Operating Mode
c.  Press the Up ñ and Down ò keys to adjust the 
displayed setpoint to the desired value.
d.  To return to the normal operating mode from 
the Adjustment Mode, when the "bc” option is 
displayed, press either the Up ñ or Down ò key.  
If no keys are pressed, after ve (5) minutes the 
Boiler Control will automatically return to the 
Operating Mode.
6.  More Information about Adjustable Parameters 
a.  High Limit (HL_)
  The Boiler Control is factory programmed with 
a High Limit Setpoint of 180°F. The boiler turns 
"off" when the boiler water temperature (bt) 
is above this value. The High Limit setpoint 
is adjustable between 140° and 240°F. The 
Operating Setpoint (P) will equal the High 
Limit Setpoint.
b.  High Limit Differential (HdF)
i.  The Cold Start Boiler Control is factory 
programmed with a Differential of 15°F. 
The Differential is the number of degrees 
the boiler temperature must decrease below 
the Operating Setpoint before the boiler 
can restart. The differential is adjustable 
between 10° and 30°F.
ii.  On Warm Start Boiler Control the High 
Limit Differential is not adjustable and is 
xed at 10°F.