Instruction manual
37
A.  GENERAL VENTING GUIDELINES 
1.  Vent system installation must be in accordance 
with these instructions and applicable provisions of 
local building codes. Contact local building or re 
ofcials about restrictions and installation inspection 
in your area.
2.  The V8H is designed to be vented into a reclay 
tile-lined masonry chimney or chimney constructed 
from type L vent or a factory built chimney that 
complies with the type HT requirements of UL103.   
The chimney and vent pipe shall have a sufcient 
draft at all times, to assure safe proper operation 
of the boiler. See Figure 18 for recommended 
installation.
a.  Install a draft regulator (supplied with boiler) 
following the instructions furnished with the 
regulator. See Figure 19 for alternate draft 
regulator locations.
b.  For Models V8H4W and V8H6W, the minimum 
recommended round chimney size from Table 
1B is one size larger than the smokebox outlet. 
For a vertical vent, place the increaser on the 
smokebox outlet collar. Otherwise, locate the 
increaser in the horizontal vent at the entrance to 
the chimney.
c.  With any new or replacement installation the 
chimney has to be considered. Chimneys that 
have a high heat loss may become less suitable 
as the heat loss of the home goes down and the 
efciency of the boiler installed goes up. Most 
homes have a chimney appropriate for the fuel 
and the era in which the home was built. That 
may have been a coal red or an inefcient oil 
red boiler built into a home without insulation 
or storm windows. With increasing fuel prices 
that home probably has been insulated and tted 
with storm windows so that the heat loss of the 
home has been reduced. This requires less fuel to 
be burned and sends less heat up the chimney.
  A new boiler probably has a higher efciency 
than the boiler being replaced. That probably 
means that the stack temperature from the 
new boiler will be lower than that from the 
old boiler and with less room air being drawn 
up the chimney to dilute the stack gases. The 
combination of a large uninsulated chimney, 
reduced ring rate, reduced ring time, lower 
stack temperature and less dilution air can, in 
some cases, contribute to the condensing of small 
amounts of water vapor in the chimney. Such 
condensation, when it occurs, can cause chimney 
deterioration. In extreme cases, the chimney 
may have to be lined to insulate the chimney and 
thus prevent the condensation. The addition of 
dilution air into the chimney may assist in drying 
the chimney interior surfaces.
  A massive chimney on a cold, or exposed outside 
wall may have produced adequate draft when it 
was red with a higher input and greater volumes 
of heated gases. With reduced input and volume, 
the draft may be severely affected. In one 
instance our research showed a new chimney of 
adequate sizing produced only .035" W.C. after 
30 minutes of continuous ring at 13.0% CO
2
. 
Outside wall chimneys take longer to heat up 
and can have .00" W.C. draft at burner start-
up. You may have to consider a special alloy 
chimney ue liner with insulation around it and a 
stabilizing draft cap or even a draft inducing fan 
in severe cases.
d.  For the same reasons as in c. above, heat 
extractors mounted into the breeching are not 
recommended.
3.  For minimum clearances to combustible materials 
refer to Figure 2.
B.  OPTIONAL AIR INTAKE PIPING 
INSTALLATION - Outdoor air for combustion may 
be provided with an optional U.S. Boiler Company 
V8H™ Fresh Air Accessory Kit (ONLY AVAILABLE 
ON BECKETT BURNERS, with plastic cover 
application, P/N 102119-01), refer to Figure 20. 
Refer to Fresh Air Accessory Kit Instructions for 
installation and air intake piping details.
WARNING
DO NOT reduce size of air intake pipe.
Read, understand and follow combustion air 
instruction restrictions contained in the Pre-
Installation Section of this manual.
1. General
a.  Use 4 inch diameter, single wall galvanized 
metal pipe and ttings available at most heating 
distributors for air intake piping. Maximum 
allowable air intake length is 50 equivalent feet. 
Each elbow is equal to 6 equivalent feet.
WARNING
DO NOT exceed maximum allowable air intake 
length.
b.  Start at Burner. Work toward air intake terminal.
c.  Maintain minimum of ¼ inch per foot slope in 
horizontal run to air intake terminal. Slope down 
toward air intake terminal.
d.  Seal all joints gas-tight, using silicone caulk or 
self-adhesive aluminum tape.
SECTION VIII: VENTING AND AIR INTAKE PIPING










