Other Suspected Main Control Faults
If other components have been ruled out as being faulty 
but the unit continues to have operating issues, it is most 
likely due to a configuration error. Configuration errors 
can be cleared by restoring the unit to its factory default 
setting. Factory defaults may be restored through the 
service menu.
CAUTION
!
Precautions must be taken while working with 
live electrical equipment. Be sure to follow 
proper safety procedures while performing tests 
on live systems.
CONVECTION COOLING
All 3000 series units are equipped with an advanced 
convection cooling system. Convection cooling stabilizes 
cabinet temperature, cools product faster and increases 
energy efficiency. 
Evaporator Fan
The evaporator fan is responsible for circulating warm air 
from the refrigeration zone, past the evaporator and back 
into the refrigerated zone. 
The evaporator fan is factory set to have a 1 minute delay 
at the beginning of a cooling cycle. This delay gives the 
evaporator time to cool properly before warm air is passed 
over it. The fan will continue to run for an additional 2 
minutes at the end of a cooling cycle. Fan delay times can 
be modified through the service menu.
Evaporator fan operation is also determined by door 
switch state. If the door switch circuit opens the fan will 
stop. When the door switch circuit is closed the fan will 
either continue running with the cooling cycle, or if not 
currently cooling, the fan will run for 1 minute to circulate 
air and clear any condensation that may have appeared 
on glass doors and shelves. 
NOTE: If the unit is set to sabbath mode the evaporator 
fan will no longer respond to the state of the door switch.
In order to operate efficiently the evaporator fan blade 
and vents should be unobstructed and free of any dust 
buildup. 