User Guide & Service Manual

USER GUIDE
 Control Operation - Service 5
u-line.com
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • SERVICE
Offsets are used to adjust or correct thermistor readings. 
Offset values are added to the current thermistor reading 
and are then used by the control board to determine 
cooling and defrost cycle times. Offsets have a range of 
+/- 10°F. Corrected values may be viewed through the 
customer “All Temps” menu.
To access Offsets
1. Press   to select “Offsets”.
2. Press .
3. Press   and   to scroll through available 
thermistors.
To change offsets
4. Press  , the selected thermistor will begin to flash.
5. Press   or   to modify offset value.
6. Press   to confirm setting.
To exit the Offset menu, press   to select “Return to 
Menu” and press   to confirm.
Self Test
Self test is used to initiate a self diagnostic report. Any 
system faults will be displayed under Self test. If no errors 
are present “no errors” will be displayed and the main 
control board is functioning properly. The main control 
board is extremely robust and should rarely require 
service. Most issues are external to the control. Reference 
troubleshooting for more information.
To access Self Test
1. Press   to select “Self Test”.
2. Press .
3. Press   and   to scroll through available 
information.
To exit the Self Test, Press   to select “Return to Menu” 
and press   to confirm.
Differentials
(DO NOT MAKE AN ADJUSTMENT TO THIS WITHOUT 
CONTACTING TECH LINE: 800-779-2955)
Differentials are used to determine the maximum variation 
from set point and have a range of 0 through 10. The 
table below shows the effect of differentials on cooling 
cycles with a set point of 45°F (7°C).
NOTE: Air temperature does not reflect product 
temperatures.
The graph below shows a unit’s cooling cycle over time 
with various differentials.
Up
Select
Down
RETURN TO MENU
SELF TEST
NO ERRORS
try “RELAY TOGGLE”
Differential Cycle Start °F (°C) Cycle End °F (°C)
0 45° (7°) 43° (6°)
1 46° (8°) 43° (6°)
2 47° (8°) 41° (5°)
3 48° (9°) 41° (5°)
4 49° (10°) 39° (4°)
5 50° (10°) 37° (3°)
Up
Select
Down
RETURN TO MENU
DIFFERENTIALS
ZONE = 1°F
Can be displayed in Celsius
p'LɞHUHQWLDO
p'LɞHUHQWLDO
p'LɞHUHQWLDO
51