User Manual

Table Of Contents
76 Tools for Configuring and Operating
Configuring and Operating with WAGO-I/O-CHECK
WAGO-I/O-SYSTEM 750
I/O Modules
Status Value Description
-127...0 RSSI value/signal strength too weak
0 Signal strength very good
Signal Strength
0...+127 Signal strength too strong
(see Appendix
6.3.6.5, "GetLinkSignalStrength")
< 39
Too many busy/defective channels
39…53 Some busy/defective channels
Available Channels
> 53 Free/undisturbed channels (low interference)
(see Appendix
6.3.6.6, "GetAvailableChannelMap")
Click on one of the fields of the last column of the table. A dialog with a de-
tailed status display for the selected slot opens (see Figure 34). Choose For all
connections by checking it to query the status of all slots.
Figure 34: Status query for slots g064475e
By selecting a certain Object group, you are limiting the status reports ac-
cordingly (see Table 34).
Table 34: Object groups and possible status reports
Object Groups Status *
Whole system Ok
Ok
Not specified
BER is moderate
BER is high
Less than 39 channels available
Less than 54 channels available
Connection error
Wireless connections
Connection interrupted