User Manual

Table Of Contents
Tools for Configuring and Operating 75
Configuring and Operating with WAGO-I/O-CHECK
WAGO-I/O-SYSTEM 750
I/O Modules
The following displays are summarized under the header "Status"
(see Table 32):
Table 32: General status display
Status Value Description
Slave Device takes over the role of "slave" Device Role
Master Device takes over the role of "master"
(see also Appendix
6.3.5.20, "GetLocalDeviceRole")
Operating Mode Communication Device is in communication mode
(see also Appendix
6.3.3.2, "GetLocalOperationMode")
Real-time profile Device is in the communication profile "real-time" Communication
Profile
Ad hoc profile Device is in the communication profile "ad hoc"
Ok No warnings/errors
Warning Warning
Error General error
Diagnostic State
Critical defect Critical error (for details see Appendix
6.3.6.1, "GetLo-
calDeviceStatus")
Ok Configured network is established.
Inconsistent Not all configured connections are established.
Network Status
Defective Configured network is (still) not established.
(for details see Appendix
6.3.6.2, GetNetworkStatus)
[Start Diagnostics]
Start value monitoring
[Stop Diagnostics]
End value monitoring
Under "Channel monitor", the transmission quality for each slot is displayed
(see Table 33):
Table 33: Status of transmission channel
Status Value Description
Slot No. Slot _ Slot Number
Yes Connected
No Not connected
Connected
No No device configured for this slot
0 % No bit error occurred
0.1…10% Some bit errors occurred
Bit Error Rate
> 10% High bit error rate