40 I/O Modules
Special Modules
WAGO-I/O-SYSTEM 750
I/O Modules
W6 has been processed in the configuration mode (ad hoc profile)
"AllowRemoteDevice" with MAC address of W6
"Cutoff" for slot 6 raised from 0 to 6
W1 W2 W4 W5 W6 W7 E2 E3
0 48
Connection to E2 is disconnected (ad hoc profile)
UnbindRemoteDevice or end device discontinues the connection
Slot assignments are not changed
The last data is retained until the next reboot
W1 W2 W4 W5 W7 E1 E2 (Data
obsolete)
E3
0 48
Control/status byte and internally used byte
The complete process image is first transmitted from the slave to the master. If
the slave has received a process image of the master, it sends only those bytes
that are still visible after the "cutoff" from this point on. It is always the visible
portion of the process image only, which is not truncated by "cutoff", that is
transmitted from the master to the slave.
Note
Missing data in the protocol header may lead to termination of the connec-
tion. Therefore, prepend the 3-byte channel information (0x01 and 0x00 and
field length) to the data to be transferred if sending from an external device to
a WAGO device. WAGO devices add the header automatically (see Section
2.1.1.7.2.4.1).