Example Configurations using WAGO-I/O-CHECK
WAGO-I/O-SYSTEM 750
I/O Modules
6.5.2.2.6 Loading the MAC Address of the Master into the Device Lists of the
Slaves
1. Enter the MAC address of the master in bytes 5 through 10 of the first
slave.
2. For each slave, set byte 4 to 0x20 (TABLE_ENTRY).
3. Use the mailbox command "AllowRemoteDevice" (opcode 0x83) to load
the master in the device list of the slave (see Table 46).
4. Proceed in the same manner with the remaining slaves.
Table 46: Mailbox command "AllowRemoteDevice"
Byte 10 9 8 7 6 5 4 Toggle Opcode empty C/S
PD/O
0x00 0x06 0xC6 0x__ 0x__ 0x__ 0x20 0x80 0x83 0x00 0x20
PD/I
0x00 0x00 0x00 0x00 0x00 0x00 0x00 0x80 0x83 0x00 0x60
6.5.2.2.7 Binding the Slaves in the Master
1. Write the MAC address of the first Bluetooth
®
slave in bytes 5 through 10
of the master (see Table 47).
2. Set byte 4 to 0x20 (TABLE_ENTRY).
3. Use the mailbox command "BindRemoteDevice" (opcode 0x85) to load the
MAC address of this slave in the device list of the master.
Table 47: Mailbox command "BindRemoteDevice" for binding Slave 1
Byte 10 9 8 7 6 5 4 Toggle Opcode empty C/S
PD/O
0x00 0x06 0xC6 0x___ 0x___ 0x___ 0x20 0x00 0x85 0x00 0x20
PD/I
0x00 0x06 0xC6 0x___ 0x___ 0x___ 0x00 0x00 0x85 0x00 0x60
4. Write the MAC address of the second Bluetooth
®
slave in bytes 5 through
10 of the master (see Table 47).
5. Set byte 4 to 0x21 (TABLE_ENTRY).
6. Change the toggle byte to 0x80 to execute the mailbox command (opcode
0x85) again.