Example Configurations using WAGO-I/O-CHECK
WAGO-I/O-SYSTEM 750
I/O Modules
6.5.2.2.1 Switch the Mailbox on
1. Switch the mailbox of all modules on by setting the control byte to 0x20
(bit 2
5
=1) (see Table 36).
Different error/warning bits can be set in the status byte depending on the de-
livery condition. The switched on mailbox is confirmed in byte 0 (status byte)
with 0x60: 60
hex
= 0110.0000
bin
! bit 2
5
and 2
6
are set
Bit 2
5
will confirm the switched on mailbox while bit 2
6
will display a still in-
active wireless connection.
Additional Information
The description of the control and status bit can be found in Section 2.1.1.8.1.1.
Table 36: Switching the mailbox on
Byte 6 5 4 Toggle Opcode empty C/S
PD/O
0x00 0x00 0x00 0x00 0x00 0x00
0x20
PD/I
0x00 0x00 0x00 0x00 0x00 0x00 0x60
6.5.2.2.2 Reset Modules to Factory Default
1. Reset all modules to the factory settings using the mailbox command "Set-
FactorySettings" (opcode 0x57) (see Table 37).
2. Wait five seconds after the execution of the command before continuing so
that the internal Bluetooth
®
subsystem can change over.
Table 37: Mailbox command "SetFactorySettings"
Byte 6 5 4 Toggle Opcode empty C/S
PD/O
0x00 0x00 0x00 0x00
0x57 0x00 0x20
PD/I
0x00 0x00 0x00 0x00 0x57 0x00 0x60
3. Execute the command "FlashRebootHost" (opcode 0x11) for all modules
(see Table 37) to restart them.
4. Wait five seconds after the execution.
Table 38: Mailbox command "FlashRebootHost"
Byte 6 5 4 Toggle Opcode empty C/S
PD/O
0x00 0x00 0x00 0x00
0x11 0x00 0x20
PD/I
0x00 0x00 0x00 0x00 0x11 0x00 0x60