I/O Modules
6.3.5.2 Write the Local Device Name (SetLocalDeviceName, 0x41)
With this command, the Bluetooth
®
name of the local bus module is set. The
normal set of ASCII characters is available.
Note
The use of special characters (e.g. word wraps) is possible but should be
avoided.
The complete device name can be a maximum of 15 characters.
The complete device name can be read and written with DLD commands
regardless of the mailbox size.
Conditions
Mailbox size Operating mode/profile Device role
6 12 18 Config.
Real-
time
Ad hoc Master Slave
Save
config.
Restart
() () - - - -
Request
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0 MBX_SETLOCALDEVICENAME
1 T -
2 MBX_NAME_LENGTH
3 CHAR1
... ...
17 CHAR15
Arguments
Parameter Value Description
MBX_NAME_LENGTH [1...15] Number of the transferred characters of the name
CHARn Characters of the device name in ASCII code
Example: "ABC"
A = CHAR1 = 0x41
B = CHAR2 = 0x42
C = CHAR3 = 0x43
Response
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0 MBX_SETLOCALDEVICENAME
1 T MBX_RESULT