Appendix 107
Mailbox Command References
WAGO-I/O-SYSTEM 750
I/O Modules
6.3.2.2 Continuation of a Block Download or Upload (DLD_CONT, 0x02)
With call up, the uploading/downloading of a block is continued. During an
upload of data to the module, the data bytes from byte 2 may be ignored.
Conditions
Mailbox size Operating mode/profile Device role
6 12 18 Config.
Real-
time
Ad hoc Master Slave
Save
config.
Restart
- - - -
Request
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0 MBX_DLD_CONT
1 T -
2 DATA
3 DATA
4 DATA
5 DATA
6 OPTIONAL DATA
... ...
17 OPTIONAL DATA
Arguments
Parameter Value Description
DATA
OPTIONAL DATA
[0x00...0xFF] Transmitted data bytes
In configuration mode, the number of data bytes is based
on the mailbox size - 2.
During a download from the module, the values of the
data bytes are ignored.