2-2 SPECIFICATIONS Manual 0-5272
2.06 Specifications & Electrical Requirements
100 Amp System
Ultra-Cut 100 XT™ Specifications & Design Features
Max OCV (U0) 425 vdc
Minimum Output Current 5 Amps
Max Output Current 100 Amps
Output Voltage 60 - 180 vdc
Duty Cycle Rating 100% @ 100A, 200V, (20kW),
Ambient Temperature
for Duty Cycle Rating
104F° (40°C)
Operating range 14°F to 122°F (-10°C to + 50°C)
Power Factor 0.94 @ 100 A DC Output
Cooling Coolant and Forced Air (Class F)
Ultra-Cut 100 XT™ Power Supply
Input Power Input Current Suggested Sizes (See Note)
Voltage Freq. 3-Ph 3-Ph Fuse (Amps) Wire (AWG) Wire (mm
2
)
(Volts) (Hz) (kVA) (Amps) 3-Ph 3-Ph 3-Ph
480 50/60 21 26 35-40 #12 4
NOTE
* Suggested wire size based on United States NFPA 70 National Electrical Code 2011 edition published by the
National Fire Prevention Association. Listings are from table 400.5(A)(2) for exible cord of certain types rated
for 75 deg C in ambient temperatures up to 30 deg C. Using wires of lower temperature rating or di� erent insu-deg C in ambient temperatures up to 30 deg C. Using wires of lower temperature rating or di� erent insu- C in ambient temperatures up to 30 deg C. Using wires of lower temperature rating or di�erent insu-
lation type may require larger wire size. De rate for higher ambient.
These are suggestions only. Always refer to your local and national codes that apply to your region for nal
determination of correct wire type and size.