Manual

ULTRA-CUT 100 XT
Manual 0-5303 INSTALLATION 3-7
A. Electromagnetic Interference (EMI)
Pilotarcstartinggeneratesacertainamountofelectromagneticinterference(EMI),commonlycalledRFnoise.This
RFnoisemayinterferewithotherelectronicequipmentsuchasCNCcontrollers,remotecontrols,heightcontrollers,
etc.TominimizeRFinterference,followthesegroundingprocedureswheninstallingmechanizedsystems:
B. Grounding
1. Thepreferredgroundingarrangementisasinglepointor“Star”ground.Thesinglepoint,usuallyonthecutting
table,isconnectedwith1/0AWG(European50mm
2
)orlargerwiretoagoodearthground(measuringless
than3ohms;anidealgroundmeasures1ohmorless.Refertoparagraph‘C’,CreatingAnEarthGround.The
groundrodmustbeplacedascloseaspossibletothecuttingtable,ideallylessthan10ft(3.0m),butnomore
than20ft(6.1m)fromthecuttingtable.
NOTE
All ground wires should be as short as possible. Long wires will have increased resistance to RF fre-
quencies. Smaller diameter wire has increased resistance to RF frequencies, so using a larger diameter
wire is better.
2. Groundingforcomponentsmountedonthecuttingtable(CNCcontrollers,heightcontrollers,plasmaremote
controls,etc.)shouldfollowthemanufacturer’srecommendationsforwiresize,type,andconnectionpointloca-
tions.
ForThermalDynamicscomponents(exceptRemoteArcStarterandGasControlModule)itisrecommended
touseaminimumof10AWG(European6mm
2
)wireoratcopperbraidwithcrosssectionequaltoorgreater
than10AWGconnectedtothecuttingtableframe.TheRemoteArcStarteruses1/0earthgroundwireandthe
GasControlModuleshoulduseminimum#4AWGwire.Theconnectionpointmustbetocleanbaremetal;
rustandpaintmakepoorconnections.Forallcomponents,wireslargerthantherecommendedminimumcan
be used and may improve noise protection.
3. Thecuttingmachineframeisthenconnectedtothe“Star”pointusing1/0AWG(European50mm
2
)orlarger
wire.
4. Theplasmapowersupplyworkcable(seeNOTE)isconnectedtothecuttingtableatthesinglepoint“Star”
ground.
NOTE
Do Not connect the work cable directly to the ground rod. Do not coil up excess ground or power cables.
Cut to proper length and reterminate as needed.
5. Makesureworkcableandgroundcablesareproperlyconnected.Theworkcablemusthaveasolidconnec-
tiontothecuttingtable.Theworkandgroundconnectionsmustbefreefromrust,dirt,grease,oilandpaint.If
necessarygrindorsanddowntobaremetal.Uselockwasherstokeeptheconnectionstight.Usingelectrical
jointcompoundtopreventcorrosionisalsorecommended.
6. Theplasmapowersupplychassisisconnectedtothepowerdistributionsystemgroundasrequiredbyelectrical
codes.Iftheplasmasupplyisclosetothecuttingtable(seeNOTE)asecondgroundrodisnotusuallyneeded,
in fact it could be detrimental as it can set up ground loop currents that cause interference.
Whentheplasmapowersupplyisfarawayfromthegroundrodandinterferenceisexperienced,itmayhelpto
installasecondearthgroundrodnexttotheplasmapowersupply.Theplasmapowersupplychassiswould
then be connected to this ground rod.
NOTE
It is recommended that the Plasma Power Supply be within 20 - 30 ft (6.1 – 9.1 m) of the cutting table,
if possible.
7. Theplasmacontrolcableshouldbeshieldedwiththeshieldconnectedonlyatthecuttingmachineend.Con-
nectingtheshieldatbothendswillallowgroundloopcurrentswhichmaycausemoreinterferencethanwithno
shield at all.