applies for UPS shutdown because of power failure. The range is from 1 to 999
seconds.
5.2.2. Remote Shutdown
This configuration is to remote shut down specific PCs which are powered by monitored
UPS.
Step 1 Select UPS Setting >> Remote Shutdown. Refer to Diagram 5-12.
Diagram 5-12
Step 2 Select remote shutdown conditions.
Step 3 Add/Delete remote system IP address.
Step 4 Click “Apply” button to save all data.
NOTE: Click “Default” button to recover the default setting.
Conditions:
UPS works on battery mode Remote systems shutdown after xx min xx sec:
When clicking the checkbox, remote systems which are powered by monitored
UPS will shut down after monitored UPS running on battery mode for xx min xx
sec. The maximum setting number for minutes is 999, and for seconds is 59.
Remote systems shutdown when UPS is at low battery level: When clicking the
checkbox, remote systems which are powered by monitored UPS will shut down