Screen 4.1: This alarm indicates that the rectifier is overloaded. The rectifier overload appears
when the input current of any phase is greater than the following ratio:
Iin-ovl = 0,326 x Pout / Vout_p-n
- Iin-ovl is Overload Input Current (A)
- Pout is Rated Output Apparent Power (VA)
- Vout_p-n is Rated Output Voltage phase-to-neutral (V)
Screen 4.2: This alarm indicates that the inverter is overloaded. The inverter overload appears
either when the output current of any phase is greater than the rated output current
Iout-ovl = Pout / (Vout_p-n * 3)
- Iout is rated Output Current (A)
- Pout is Rated Output Apparent Power (VA)
- Vout_p-n is Rated Output Voltage phase-to-neutral (V)
or when the total output active power is greater than the following formula.
Pact_out-ovl = Pout x 0,8
- Pact_out-ovl is the Overload Output Active Power (W)
- Pout is Rated Output Apparent Power (VA)
Screen 4.3: This alarm appears when the input the unit is under main failure condition and the level
of battery is lower than 11,5V/bat.
Screen 4.4: This alarm appears when the inverter output voltage phase to neutral in any phase is
out of margins over +/-6%
Screen 4.5: This alarm appears when there is an offset voltage higher than 5V, in any phase of the
inverter output voltage phase to neutral.
Screen 4.6: When the maintenance bypass switch is ON the UPS inverter will not be available.
Screen 4.7: The mains failure occurs when in any phase, the input voltage phase to neutral is out of
the set margins (+15%/20% by default) or the input frequency is out of the set margins (± 0,5Hz
by default).
Screen 4.8: When the inverter or PFC temperature sensors measure temperatures over the
programmed values (70ºC by default).
Screen 4.9: This message appears when the battery switch is OFF and the DC bus is charged to the
battery voltage level, to inform the user to switch ON the battery switch.
Screen 4.10: This screen indicates that the bypass input voltage or the bypass input frequency are
out of margins. These margins are programmable but by default the bypass voltage range is
+12%/17% and the bypass frequency range is ±0.5Hz.
Screen 4.11: The UPS is on bypass for any reason. It must be restarted by display keypad