6-3-3. ‘‘PARAMETERS’’ level (screen menu 3.0). See Fig. 33.
Screen 3.1: In the first row you can program the time “hh:mm:ss” (hours/minutes/seconds) and in
the second row you can program the date “dd/mm/yy” (day/month/year).
Screen 3.2: In the first row you can select the display language between the following options:
“Español”
“English”
“Francais”
In the second row you can program the Modbus Address. The range of addresses goes from 1 to 247.
Screen 3.3: n this screen you can program the BAUD RATE of communication port #0. The options
are the following:
‘’1200’’
‘’2400’’
‘’4800’’
‘’9600’’
‘’19200’’
Screen 3.4: In this screen you can program the PARITY type of communication port #0. The
options are the following:
‘’NONE”
‘’ODD’’
‘’EVEN’’
Screen 3.5: In this screen you can program the number of STOP BITS of communication port #0.
The options are the following:
‘’1’’
‘’12’’
Screen 3.6: In this screen you can program the protocol type of communication port #0. The
options are the following:
‘’SEC’’
‘’MODBUS’’
Screen 3.15: This is the screen for programming the frequency of the automatic battery test. The
options to be programmed are the following:
‘’DISABLED’’: The automatic battery test is
disabled
‘’WEEKLY’’: The automatic battery test runs
once per week
‘’MONTHL’’: The automatic battery test runs
once per month
‘’YEARLY’’: The automatic battery test runs
once per year.
Screen 3.16: This screen appears independently on the last screen, but it only has sense to be
programmed if the automatic battery test runs once per week. The options to be programmed are
the following.
‘’MON”: Monday