User manual

- «Dischar.» Mains failure. UPS running on back-up mode (rectifier stopped, inverter running).
Origin of the output:
- «OFF» No voltage supplied at the output (either EPO pressed, or severe problem on the unit).
- «Invert» Inverter voltage is supplied at the output. Loads are protected
-«Bypass» Bypass voltage is supplied at the output. Either the unit is manually stopped, or
overloaded, or other possible problems on the inverter
In the second row we have information about the configuration (single or parallel) of the unit:
Configuration and status of the unit:
- «Single:» “Single” connection.
- «Parallel-Single» Parallel connection. Unit is on “single” state.
- «Parallel-Master» Parallel connection. Unit is on “master” state.
- «Parallel-Slave» Parallel connection. Unit is on “slave” state
Examples:
a) b)
Screen 0.2: Internal firmware versions of both Digital Signal Processor (“DSP Ver:”) and
microcontroller (“uC Ver:”). In the sample screen, “ver. 3.2 a” and “ver. 2.4 b” respectively.
Screen 0.3: UPS Serial Number, expressed with 10 characters. Possible characters ranges are
“0”-“9”, “A-“Z” and also “ “ (blank space), “-“. See sample screen
When pressing key (ESC) from any screen of any submenu, we go back to main screen (Screen 0.0),
Fig. 30. Screen 0.0 «Initial» and its submenus.
6-3-2. ‘‘CONTROL & STATUS OF THE UNIT” Level (screen menu 1.0). See Fig. 31.
Screens 1.1, 1.3 and confirmation screen (1.2 / 1.4): to start and stop the unit through the
control panel..
For procedure for starting and stopping, see chapters 5.1.2 and 5.2.
Screen 1.5 and confirmation screen (1.2 / 1.4): to order a battery test. On the second row,
information about the battery test is given. Possible messages:
“NOT AVAILABLE“:The battery test is not available.
“PRESS <ENTER>“: Press <ENTER> to run the battery test.
“EXECUTING“:The battery test is running.
“SUCCESSFUL“:The battery test has been successful..
“NOT SUCCESSFUL”: The battery test has not been successful.
UPS: Normal, Invert.
CFG: Single
UPS: Shutdown, Bypass
CFG: Parallel-Master
screen 0.0
()
()
Model Name
11:19:35 08/10/2009
()
()
screen 0.1
UPS:
CFG:
()
()
screen 0.2
DSP Ver.: ver. 3.2 a
Uc Ver.: ver. 2.4 b
screen 0.3
UPS Serial Number
09 A-321899