User manual
Never manipulate with your hands or through conducting objects, do not short the battery terminal
block or the battery enclosure.
Never short the battery terminals as it involves a high risk. It involves the detriment of the
equipment and batteries
Avoid mechanical efforts and impacts
Do not open or mutilate the battery. Released electrolyte is harmful to the skin and eyes.
Do not dispose of batteries in a fire. The batteries may explode.
In case of contact of the acid with parts of the body, wash immediately with plenty water and call
urgently the nearest medical service
Batteries involve a serious risk for the health and for the environment. Their disposal should be done
according to the existing laws.
4-1-2. To get into account
All the UPS units and the battery packs have terminals as power connection parts, and DB9
connector for the communication channel, located in the inside of the equipment. Follow the steps
described next to have access to them:
Unlock the lock (CL) with the special given key.
Rotate it 45º to clockwise and open the frontal door (PF) completely. DB9 connectors from
communication ports and terminals for remote EPO button will be uncovered.
Remove the screws (t1), which are fixing the terminal cover (TB) inside of the cabinet and move it
away; the power terminals will be uncovered.
Model
Equipment
power
(kVA)
Maximum input and bypass current, and nominal output current (A)
220 V
230 V
240 V
Input
Output
Bypass
Input
Output
Bypass
Input
Output
Bypass
UPS-15
15
66
69
-
64
65
-
60
63
-
UPS-20
20
90
90
-
85
87
-
84
84
-
UPS-30
30
132
132
-
128
130
-
120
123
-
UPS-40
40
177
177
-
170
174
-
159
165
-
UPS-50
50
222
222
-
213
217
-
201
204
-
UPS-60
60
287
287
-
255
261
-
240
246
-
UPS-80
80
357
357
-
340
348
-
323
331
-
UPS-15-B
15
66
69
69
64
65
65
60
63
63
UPS-20-B
20
90
90
90
85
87
87
84
84
84
UPS-30-B
30
132
135
135
128
130
130
120
123
123
UPS-40-B
40
177
183
183
170
174
174
159
165
165
UPS-50-B
50
222
228
228
213
217
217
201
204
204
UPS-60-B
60
267
273
273
255
261
261
240
246
246
UPS-80-B
80
357
365
365
340
348
348
323
331
331
Table 1. Input, output and bypass currents for standard single phase voltage UPS.